Revision 02-15-2019
3
1. Setting the Lower Limit
Now that you have finished calibrating the upper FLA% you may now work on setting the minimum FLA% limit.
a.
Begin by turning the LOAD relay manually OFF, and
UNLOAD relay manually ON.
b.
Wait until the compressor is fully unloaded and then
check the FLA% value in the circuit grid.
c.
Take this number, double click on the “Value” column for setpoint #31 “MIN FLA %” and set this number
as the new value.
(Note: if you have multiple compressors you should use an average of their fully unloaded values).
Set new value here
for MIN FLA%
CLICK SEND CHANGE