71
for more detail.
5.4 Selection of magnetic contactor
Please refer to AC3 specification, compressor selection program and design conditions of system to choose suitable
contactor.
5.5 Grounding
There
’s a grounding terminal inside cable box. Please accurately connect it to grounding of control panel for the
system.
2
8
(Option)
A:PTC
B:Pt100Ω / Pt1000Ω
PW2:7,8,9
PW1:1,2,3
3
9
Earth Bolt
1
7
B
A
Suggestion:
a. The regular setting of electric leak protection should be greater than 50mA; for a humid location, 25mA is
better.
b. Grounding voltage of casing should be no greater than 50V; for a humid location, the limit is 25V.
c. Grounding resistance should be no greater than 500 Ohm.
d. Air cut board (ACB) is regularly equipped with electric leak protection. Please refer to related settings for its
normal action.
e. If electric leak protection is active, please check if insulation of equipments is normal and if its wiring and
setting are correct. Please make sure nothing is wrong before turning on the power. If there are any questions,
please contact the supplier of equipments.
Grounding Terminal
Summary of Contents for RC2-F Series
Page 6: ...5 2 2 Compressor outline...
Page 7: ...6...
Page 8: ...7...
Page 9: ...8...
Page 10: ...9...
Page 11: ...10...
Page 12: ...11...
Page 13: ...12...
Page 14: ...13...
Page 15: ...14...
Page 16: ...15...
Page 17: ...16...
Page 18: ...17...
Page 19: ...18...
Page 20: ...19...
Page 21: ...20...
Page 22: ...21...
Page 23: ...22...
Page 24: ...23...
Page 25: ...24...
Page 26: ...25...
Page 27: ...26...
Page 85: ...84 Horizontal External Oil Separator OS80 Horizontal External Oil Separator OS100 OS125 OS150...