Technical Manual
VERSION 2.0 -10-18-2018
10
2.7 3 or 4step capacity control system
There are two (For RC2100, RC2140, RC2180) or three (for the rest 23 models) solenoid valves installed on the
compressor that control the compressor capacity from minimum capacity (please refer to chapter 2.2 for different
minimum capacity of each model) to full load (100%). There are two / three normally closed (NC) solenoid valves used
to control the various required capacity. For the compressor with 3step / 4step capacity control system, it is usual to
use the sequence of min.%66%100% / min.%50%75%100% to load the capacity of compressor and to use the
sequence of 100%66%min.%/100%75%50%min% to unload the capacity. If min% capacity is kept for a long time,
the problem of oil return, motor cooling, high discharge temperature need to be solved by adding accessories such as
oil level switch for monitoring the oil level, liquid injection devices for cooling motor coil and reducing discharge
temperature.(Figure 8). Min% is recommended for start and stop only, not for longtermed operation.
Figure 8 4step capacity control
Note: For 3step or 4step capacity control system, Hanbell equips normallyclosed (NC) solenoid valves as standard
accessory. If normallyopened (NO) solenoid valves are preferred instead, please specify it to Hanbell when placing
order.
a. min% capacity
When starting the compressor, SV25%/33% solenoid valve is
energized and the piston is in min% capacity position, so even the oil
coming from the oil sump is continuously injecting into the cylinder
through the capillary, the highpressured oil in the cylinder bypasses
directly into the suction port, so the piston is kept in its initial position.
※
It is strongly recommended to energize SV25%/33% solenoid valve for 1~3 minutes before starting the compressor
to ensure the slide valve is in min% position.
b. 50% capacity (omitted for RC2100, 140,180)
When SV50% solenoid valve is energized by the temperature
controller, the highpressure oil in the oil sump flows into the cylinder
due to the closing of min% valve that pushes the piston moving toward
the position where a hole at exactly 50% position drains the oil back to
the suction side then the piston is held on that position.
No. Component
No. Component
No. Component
1 Suction filter
7 Discharge bearings
13 Capillary
2
Gas in
(
low
pressure
)
8 Oil separator baffle
14 Solenoid valve (min. %),
SV 25%/33%
3 Motor
9
Gas out
(
high pressure with
oil
)
15 Solenoid valve (50
%
of full
load),SV50
%
4 Oil filter
cartridge
10 Lubricant
16 Solenoid valve (75
%
/66% of full
load),SV75
%
/66%
5 Suction
bearings
11 Oil separator demister
17 Slide valve
6 Male rotor
12 Gas out(high pressure without
oil)
*
For RC2100, 140 & 180 the
SV 50
%
omitted
RC2100,140,180 capacity
control system
SV33%(NC)
SV66%(NC)
100
%
of full load
not energized not energized
66% of full load
not energized
energized
33%
(
for start
)
energized
not energized
RC2200~1530 capacity
control system
SV25%(NC) SV75%(NC) SV50%(NC)
100
%
full load
not energized not energized not energized
75
%
of full load
not energized energized not energized
50
%
of full load
not energized not energized energized
25
%
(
for start
)
Energized not energized not energized
SV 50% OFF
SV75% OFF
SV25%/33% ON
Figure 9 Min% Capacity
SV50% ON
SV75% OFF
SV25%/33% OFF
Figure 10 50% Capacity
Summary of Contents for RC2 Series
Page 24: ...Technical Manual VERSION 2 0 10 18 2018 24 UNIT SI mm Imperial in UNIT SI mm Imperial in ...
Page 25: ...Technical Manual VERSION 2 0 10 18 2018 25 SI mm Imperial in UNIT UNIT SI mm Imperial in ...
Page 26: ...Technical Manual VERSION 2 0 10 18 2018 26 SI mm Imperial in UNIT UNIT SI mm Imperial in ...
Page 27: ...Technical Manual VERSION 2 0 10 18 2018 27 UNIT SI mm Imperial in ...
Page 28: ...Technical Manual VERSION 2 0 10 18 2018 28 ...
Page 29: ...Technical Manual VERSION 2 0 10 18 2018 29 UNIT SI mm Imperial in ...
Page 30: ...Technical Manual VERSION 2 0 10 18 2018 30 ...
Page 31: ...Technical Manual VERSION 2 0 10 18 2018 31 ...
Page 32: ...Technical Manual VERSION 2 0 10 18 2018 32 ...
Page 33: ...Technical Manual VERSION 2 0 10 18 2018 33 ...
Page 34: ...Technical Manual VERSION 2 0 10 18 2018 34 UNIT SI mm Imperial in ...
Page 35: ...Technical Manual VERSION 2 0 10 18 2018 35 2 RC2 B outline drawings ...
Page 36: ...Technical Manual VERSION 2 0 10 18 2018 36 ...
Page 37: ...Technical Manual VERSION 2 0 10 18 2018 37 ...
Page 38: ...Technical Manual VERSION 2 0 10 18 2018 38 ...
Page 39: ...Technical Manual VERSION 2 0 10 18 2018 39 ...
Page 40: ...Technical Manual VERSION 2 0 10 18 2018 40 ...
Page 41: ...Technical Manual VERSION 2 0 10 18 2018 41 ...
Page 42: ...Technical Manual VERSION 2 0 10 18 2018 42 ...
Page 43: ...Technical Manual VERSION 2 0 10 18 2018 43 ...
Page 44: ...Technical Manual VERSION 2 0 10 18 2018 44 SI mm Imperial in UNIT ...
Page 60: ...Technical Manual VERSION 2 0 10 18 2018 60 ...
Page 83: ...Technical Manual VERSION 2 0 10 18 2018 83 NOTES ...