4
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
2.3 Compressor specifications
Model
RT-120
(E,T)
RT-130
(E,T)
RT-140
(E,T)
Refrigerant
R134a
Compressor
Type
Two-stage with speed-up gearing
Pressure ratio*
LP
HP
LP
HP
LP
HP
1.63 1.55 1.63 1.55 1.63 1.55
Mass flow rate*
kg/sec 11.95 13.54 13.01 14.73 13.43 15.21
Volume flow (Suction)*
㎥
㎥
㎥
㎥
/hr
2,466 1,740 2,684 1,893 2,711 1,954
Rated speed
rpm
11,700
12,000
12,000
Inlet guide vane control IGV1
10~100% continuous(standard, *2)
Inlet guide vane control IGV2
10~100% continuous(optional, *3)
Transmission
Type
Helical gear
Lubrication
Built-in oil pump
Lubricant charge
Liter
38
Motor
Type
3 Phase, 2 Pole, Induction
Starting
Y-
△
△
△
△
Starting, Direct starting
Voltage (50/60 Hz)
V
380~600,10k/6k/4k/3k
Insulation
Class F
Protection
PTC,Pt100/Pt1000
Oil heater
kW
2x0.5
Chamber heater
kW
2x0.3
Maintenance butterfly valve
8” (optional)
Dimension (LxWxH)
m
2.30 x 1.20 x 1.02
Weight
kg
3,500
Hydrostatic pressure test
kg/cm²g
22
Table 2.1 Refrigeration Compressor specifications
1. Under CT/ET=36
℃
/6
℃
(refer to ASHRAE 90.1-2015)
2. Setting IGV1=5% applied only in startup, in regular operation should set IGV1
10%
≧
,
while for Dual IGV models IGV1
5%.
≧
3. IGV2 is optional, for Dual IGV models select RT-120T, RT-130T, RT-140T. These
models have good part load efficiency with IPLV=7.0~7.4
4. The available motor voltage specification is as follows
:
Voltage
RT-120~140(E,T)
380V~600V
○
○
○
○
3kV/3.3kV
○
○
○
○
6kV/6.6kV
○
○
○
○
10kV/11kV
○
○
○
○