74
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
2. Soft-starter could set up the starting time, longer the starting time, less the ampere it has.
For more details, please refer to technical documents of each manufacturer.
●
Direct start
1. When the high voltage motor adopts full voltage starting, the starting current is about 6~7
times of the motor rated current.
●
Step-down start
1. High voltage motor could operate with high voltage step-down transformer. Any technical
advice, please contact Hanbell.
5.3.3 Motor design
:
:
:
:
Direct on line start/soft start/inverter start
RT series compressors with high voltage motors can start by direct start as below
shown.
Figure 5.9 Wiring for high voltage
RT series compressors with low voltage motors can start by Y-
Δ
start, soft start and
inverter start as below shown.
Figure 5.10 Wiring for low voltage
Note: In case of soft start and inverter start, bridges must be installed for wring of the same
phase to prevent current imbalance.