6
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
Model
RT-240
(E)
RT-260
(E)
RT-280
(E)
Refrigerant
R134a
Compressor
Type
Two-stage with speed-up gearing
Pressure ratio*
LP
HP
LP
HP
LP
HP
1.63 1.55 1.63 1.55 1.63 1.55
Mass flow rate*
kg/sec 23.91 27.08 26.18 29.65 27.36 30.99
Volume flow (Suction)*
㎥
㎥
㎥
㎥
/hr
4,933 3,480 5,402 3,810 5,645 3,982
Rated Speed
rpm
8,200
Inlet guide vane control IGV1
10~100% continuous
Inlet guide vane control IGV2
Not applicable
Transmission
Type
Helical gear
Lubrication
Built-in oil pump
Lubricant charge
Liter
68
Motor
Type
3 Phase, 2 Pole, Induction
Starting
Y-
△
△
△
△
Starting, Direct starting
Voltage (50/60 Hz)
V
380~600,10k/6k/4k/3k
Insulation
Class F
Protection
PTC,Pt100/Pt1000
Oil heater
kW
2x0.5
Chamber heater
kW
2X0.3
Maintenance butterfly valve
10” (optional)
Dimension (LxWxH)
m
2.60 x 1.30 x 1.20
Weight
kg
4,500
Hydrostatic pressure test
kg/cm²g
22
Table 2.3 Refrigeration Compressor specifications
1. Under CT/ET=36
℃
/6
℃
(refer to ASHRAE 90.1-2015)
2. Setting IGV1=5% applied only in startup, in regular operation should set IGV1
10%,
≧
3. Dual IGV structure is not available for this framework.
4. The available motor voltage specification is as follows
:
Caution
:
This series of low-voltage motor specifications are only for motor A. Motor B with
high evaporation conditions is not applicable due to low voltage start up and extremely
large running current.
Voltage
RT-240~280
380V~600V
Optional
3kV/3.3kV
○
○
○
○
6kV/6.6kV
○
○
○
○
10kV/11kV
○
○
○
○