7
Vol. 2.6 © 2020 Hanbell Precise Machinery Co., Ltd. All rights reserved
Model
RT-111
RT-161
RT-221
Refrigerant
R134a
Compressor
Type
Two-stage with speed-up gearing
Pressure ratio*
LP
HP
LP
HP
LP
HP
1.91 1.73 1.91 1.73 1.91 1.73
Mass flow rate*
kg/sec 9.83 11.74 17.03 20.35 19.66 23.48
Volume flow (Suction)*
㎥
㎥
㎥
㎥
/hr
2,028 1,296 3,515 2,246 4,056 2,592
Rated Speed
rpm
12,000
9,400
Inlet guide vane control
IGV1
5~100% continuous(standard, *2)
Inlet guide vane control
IGV2
5~100% continuous(standard, *3)
Transmission
Type
Helical gear
Lubrication
Built-in oil pump
Lubricant charge
Liter
33
57
57
Motor
Type
3 Phase, 2 Pole, Induction
Starting
Y-
△
△
△
△
Starting, Direct starting
Voltage (50/60 Hz)
V
380~600,10k/6k/4k/3k
Insulation
Class F
Protection
PTC,Pt100/Pt1000
Oil heater
kW
2x0.5
Chamber heater
kW
2x0.3
Maintenance butterfly valve
8” (optional)
10” (optional)
Dimension (LxWxH)
m
2.60 x 1.30 x 1.20
Weight
kg
4,500
Hydrostatic pressure test
kg/cm²g
22
Table 2.4 Heating Compressor specifications
1. Under CT/ET=36
℃
/6
℃
(refer to ASHRAE 90.1-2015)
2. Setting IGV1=5% applied only in startup, in regular operation should set IGV1
10%,
≧
3. All standard heat pumps include dual IGV structure.
4. The available motor voltage specification is as follows
:
Caution
:
RT-221 low-voltage motor is only for motor A. Motor B with high evaporation
conditions (due to extremely large start up current) is not applicable.
Voltage
RT-111 ~ 161
RT-221
380V~600V
○
Optional
3kV/3.3kV
○
○
6kV/6.6kV
○
○