6.3 Compressor protection device
Protection devices as below table are basic configuration (depends on the order). Must
build up protection setting as this security requirement. You shall take their own risk if
changes the setting without our permission.
Compressor device
Setting point
Note.
Compressor motor protector
( PTC sensor)
Trip temp.:110
℃
, Return temp.:100
℃
Standard
Reverse phase protection
(protector INT69HBY)
Standard
phase failure protection
(protector INT69HBY)
Standard
Oil filter pressure difference
switch
Trip pressure: 1.5kg/cm
2
Optional
Motor temp. sensor
Pt10/Pt1000(motor liquid
injection usage)
Temp. control 30~90
℃
Standard
˙
Manual reverse setting(recommended):
As compressor protection device. Compressor motor coil protection and compressor
discharge temperature must connect with INT69HBY connector. In case it can react
immediately when the temperature tripped. And set up the guiding light on control box.
Turning on the compressor at shorted circuit to bypass protection module is not allowed,
and Hanbell is not responsible for the damage.