Sensitivity volume
:
※
ZERO/SPAN Setting
:
Remark
:
1.
Before the compressor is shipped out from the factory, the zero and span knobs have been adjusted
to the best position. Do not adjust if not necessary. If adjustment is required, please use a small
screwdriver to turn gently (excessive force will cause damage in the knob).
2. When adjusting IGV, turn to the fully-close position and then do fully-open position adjustment.
※
Note
:
Because the forward turn of the actuator is opposite to the IGV connecting rod’s, the zero
knob is fully opened while the span knob is fully closed. To avoid risk, this adjustment should be done
by qualified personnel.
3.2.5 Troubleshooting
TROUBLE
PROBABLE CAUSE
SOLUTION
Motor does not start up
1.
Power failed or dropped
2.
Signal failed or dropped
3.
Wire broken or disconnected
4.
Thermal protector functioned
5.
Limit switches functioned at an intermediate
position
6.
Motor advancer defective
7.
Control pack defective
1.
Check and supply power
2.
Check and input signals
3.
Change the wire or re-connect the
terminal
4.
Lower the ambient temperature
5.
Decrease duty rate
6.
Eliminate overload at valve
7.
Re-adjust the limit cam
8.
Change advancer (condenser)
9.
Change control pack
Sensitivity volume
* Sensitivity volume
Clockwise for higher
Counter clockwise for lower
* Max. sensitivity:
Resolution = 1/400
* Min. sensitivity:
Resolution = 1/100
SPAN Setting
ZERO Setting
* ZERO volume
CW = To increase (to OPEN direction)
Adjustable range - 25 ~ +25 %
* SPAN volume
CW = To increase (to OPEN direction)
Adjustable range - 50 ~ +200 %