Vol. 1.2 © 2020 Hanbell Precise Machinery Co., Ltd.
All rights reserved
Power Cable (mm
2
)
Grounding Wire(mm
2
)
120 and lower
16
150 and higher
25
Table 4.3 Power cable cross-sectional area
Note
:
Resistance of grounding should not be higher than 8
Ω
4.4.4 Cable of main power input
Power cable should meet the IECA S-19-81 standard, 600V insulated wire, Hypalon. Please choose
wiring size of power supply under 1.25 safety margin of maximum load. Wire diameter,
cross-sectional area, and current can refer to table 5.2. All on-site supply of cables and wires,
equipment and field wiring, cable wire terminals and equipment are necessary to comply with various
regulations and engineering requirement. Power cables shall be with braid sleeve and able to avoid the
interference with others. The power cable connection is showing on figure 4.6. Please double check the
phase sequence when wiring.
Note
:1.
The power cable gland should be insulated properly with heat shrinking tube
2.
The power cable shall sustain the maximum permissible current under 90
℃
(40
℃
ambient
temperature)
600V Hypalon Cable (*1C)
Section Area
(mm
2
)
Maximum
Permissible
current(A)
Section Area
(mm
2
)
Maximum
Permissible
current(A)
50
200
150
410
60
230
200
500
80
280
250
570
100
330
325
670
125
370
400
760
Table 4.4 600V Hypalon Maximum Permissible current
Figure 4.6 Power Terminal Connector
M16 Power Bolt