[文件標題]
[日期]
28
Vol. 1.2 © 2020 Hanbell Precise Machinery Co., Ltd.
All rights reserved
Figure 5.1 Compressor control connection
5.1 Magnetic Bearing Controller (MBC) info
Length (mm)
305
Width (mm)
360
Height (mm)
445
Weight (kg)
27
IP protection degree (*For storage, IP 2X or higher level is
required)
IP 1X (Body)
Operation Temp. (
℃
)
+5~+40
℃
Relative humidity (%)
30%~70%
Storage Temp. (
℃
)
-25
℃
~+55
℃
Power
350~750 VDC
Max. power output
1500W
Relay dry contact output
250 VAC/0.25A max or
30 VDC/2A max
Protocol
ModBus RS485
,
Cable length<100m
5.2 MBC installation notice
※
Please keep the installation space for MBC as figure 5.3 below for good cooling effect.
※
Please keep MBC located at least 400mm from the ground.
※
Keep dust, oil, water away from MBC.
※
MBC should installed in a stable place without vibration.
※
Make sure the MBC is operated within proper relative humidity to avoid the electronic components
damage.