CAN Interface ("Interface" = 1)
The following parameters are defined for the CAN interface:
"Param"
Parameter name
Allowed values
0,
Note 1
Device ID (Read only)
N/A
1
CANopen address
1 to 127
2
Bit rate
10, 20, 50, 125, 250, 500, 800 and
1000 kbit/sec.
Notes for the interfaces 0 (serial) and 1 (CAN)
Note 1: Identical to the ID command.
Note 2: Identical to the BR command.
Note 3: Identical to the AD command.
Note 4: Identical to the TD command.
Note 5: Parity check/generation is only available for Modbus RTU.
Examples:
Master (PC / PLC) sends
Slave (LDx) responds
Meaning
NS_0_0
D:1790
The device type is LDU 179
NS_0_1
B 115200
The serial channel baud rate is 115200
NS_0_2
A:000
The serial channel address is 0
NS_0_3
S 00000
The serial channel mode is ASCII
protocol and full duplex.
NS_0_1_230400
OK
Set the serial channel baud rate to
230400
8.10.4. BR Baud Rate
– Serial channel
[ n.a. ]
With this command the following baud rates can be setup: 9600, 19200, 38400, 57600, 115200, 230400 and
460800 Baud.
Master (PC / SPS) sends
Slave (LDU 179.1) responds
Meaning
BR
B 115200
Request: 115200 Baud (= factory default)
BR230400
OK
Setup: 230400 Baud
Factory default:
115200 baud
Note:
After editing the baud rate you first have to save the changes (command WP) and then restart the
device.
8.10.5. DX Full Duplex
– Serial channel
[ n.a. ]
The LDU 179.1
always
operate in full duplex mode.
Master (PC / SPS) sends
Slave (LDU 179.1) resp.
Meaning
DX
X:001
Request: DX = 1 (Full duplex, factory default))
DX1
OK
Setup: DX = 1 (Full duplex)