F o r y o u r s a f e t y
Scope of validity:
Users outside of Germany should:
- see these listed safety rules as the main ones in practice,
- compare these rules with the valid local regulations and
- carrying out the required amendments.
-
Always disconnect power supply before
carrying out any work on the Duschtempel
®
.
- Before initial use read the installation instructions.
- The electrical installation and all tests must be done
according to current valid local regulations. All work has
to be carried out by an authorised person.
- The entire electrical supply runs via a 230 V/50 Hz AC
power supply and must be protected by2-pole residual
current operated circuit breaker with a 30 mA fault
current with a separate10A fuse protection.
- The transformer is fitted with a 3-pin, earthed mains
plug. The earthed plug provides an earthing conductor
connection. This is a safety precaution. If no earthed
socket is provided, a suitable earthed socket has to be
installed by an electrician.
- It is essential that the hot - and cold water supply pipes
and the steel shower tray are earthed.
- It is forbidden to replace a damaged mains connection,
the transformer cannot be operated.
- Send defective transformer to the manufacturer or call the
technical service, the same is required if a fuse is
released.
- The transformer and the plug should be installed outside
the bathroom in an accessible area. The Transformer
comes with approx. 7 m connecting cable.
- Lay the hollow pipe from the transformer to the Dusch-
tempel
®
with a fall, to prevent incoming spray. The
hollow pipe should measure a minimum 25 mm inner-
diameter.
- The transformer rated output is 81 VA. The atmospheric
temperature should not exceed 40 °C, provide sufficient
ventilation. The transformer needs the following space:
Height approx. 100 mm, ground area approx. 150 mm
x 150 mm.