background image

10

f)  record the equipment, thermometer etc. used for 

the measurements

 

Table A: Guide to maximum stabilised tem-

peratures  recorded  during  site  tests 

 

Application 

Mixed water

 

temperature

Shower 

43°C

Washbasin 

43°C 

Bath (44°C fill) 

46°C

Bath (46°C fill) 

48°C

 

 

The mixed water temperature at terminal fitting should 
never exceed 46ºC.

If there is a residual flow during the commissioning or 
the annual verification (cold water supply isolation test), 
then this is acceptable providing the temperature of 
the water seeping from the valve is no more than 2°C 
above the designated maximum mixed water outlet 
temperature setting of the valve.
Temperature readings should be taken at the normal 
flow rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully 
submerged in the water that is to be tested.
Any TMV that has been adjusted or serviced must be 
re-commissioned and re-tested in accordance with the 
manufacturers' instructions.

Commissioning  and  in-service 

tests

Commissioning

Purpose

Since the installed supply conditions are likely to be 
different from those applied in the laboratory tests it is 
appropriate, at commissioning, to carry out some simple 
checks and tests on each mixing valve to provide a 
performance reference point for future in-service tests.

Procedure

1. 

Check that:

a) the designation of the thermostatic mixing valve 

matches the intended application

b)  the supply pressures are within the range of ope-

rating pressures for the designation of the valve

c)  the supply temperatures are within the range per-

mitted for the valve and by guidance information 
on the prevention of legionella etc.

2. 

Adjust the temperature of the mixed water in accor-
dance  with  the  manufacturer’s  instructions  and  the 
requirement of the application and then carry out the 
following sequence:

a)  record the temperature of the hot and cold water 

supplies

b)  record the temperature of the mixed water at the 

largest draw-off flow rate

c)  record the temperature of the mixed water at a 

smaller draw-off flow rate, which shall be measu-
red

d)  isolate the cold water supply to the mixing valve 

and monitor the mixed water temperature

e)  record the maximum temperature achieved as a 

result of (d) and the final stabilised temperature

 

NOTE: The final stabilised mixed water temperature 
should not exceed the values in Table A.

Summary of Contents for Ecomax Bath / Shower

Page 1: ...EN Instructions for use assembly instructions Ecomax Bath Shower 14242000...

Page 2: ...n service tests 11 Thermostatic Adjustement Temperature Limitation 12 Callibrating Thermostat 12 13 Operating your Thermostat 14 AssemblingandOperatingtheDiverterFixingDevice 15 Cleaning 16 Spare Part...

Page 3: ...hildren well away from the work area Check for hidden pipes and cables in the wall before drilling holes The unit must be mounted on a finished waterproofed wall surface usually tiles If you are using...

Page 4: ...1 Ecomax Bath Shower 2 Mesh washers 3 Flow limiter when assembling the flow limiter the TMV2 certificate is invalid 4 Diverter fixing device Optional accessories 5 Escutcheons 6 S unions 7 Pillar uni...

Page 5: ...uildCert TMV scheme recommends the following set maximum mixed water outlet temperatures for use in all premises 44 C for bath fill but see notes below 41 C for showers 41 C for washbasins 38 C for bi...

Page 6: ...1 0 10 bar Unvented System pressure balanced 1 0 10 bar Pumped System 1 0 10 bar IMPORTANT If you install this mixer with a gravity fed system there must be a minimum head vertical distance from the...

Page 7: ...7 Unvented System pressure balanced Pumped System...

Page 8: ...8 Bath Shower Thermostat 180 mm Installation 36 39 mm Seal Shower Thermostat PTFE tape 150 mm HOT COLD 1 2 3 4...

Page 9: ...s 6 Fasten the thermostatic mixer onto the S unions using the union nuts Align the unit and tighten the nuts be careful not to damage the chrome finish The S unions allow inaccuracies to be compensate...

Page 10: ...o be different from those applied in the laboratory tests it is appropriate at commissioning to carry out some simple checks and tests on each mixing valve to provide a performance reference point for...

Page 11: ...performing the in service tests is 1 year maximum General In the absence of any other instruction or guidance on the means of determining the appropriate frequency of in service testing the following...

Page 12: ...er correct installation the outlet temperature of the water can never exceed 43 C To guarantee a smooth running of the thermostatic element it is necessary from time to time to turn the ther mostat fr...

Page 13: ...spindle until the required maximum tem perature is reached 40 C You will need to use a thermometer fig 4 6 Replace the locking ring back onto the spindle as shown Refit the circlip fig 5 7 Replace th...

Page 14: ...k wise to increase the water temperature and clockwise to decrease the water temperature Thermostat The valve automatically adjusts for changes in flow supply and maintains the outlet set water temper...

Page 15: ...the diverter from below with a screw driver and screw off the diverter knob fig 1 Assemble the diverter fixing device fig 2 Assemble the diverter knob fig 3 To divert the water flow to the hand shower...

Page 16: ...e cleaning agent manufacturers have to be followed absolutely Cleaning has to be carried out with a specified cleaner dosage contact time object related and adapted to the needs The building up of cal...

Page 17: ...e Parts Ecomax Bath Shower 14242000 96633000 92929000 97469000 97335000 97163000 96488000 97164000 97210000 96922000 97211000 96644000 97510000 98163000 15x2 98421000 28x1 5 Test Certificate WRAS 1424...

Page 18: ...er pipe or vice versa when mixer is closed Backflow preventers dirty or leaking Clean backflow preventers exchange if necessary Spout temperature does not correspond with temperature set Thermostat ha...

Page 19: ...grohe will remedy this defect free of charge You will find the conditions and details of this guarantee at www hansgrohe int com guarantee Please contact your contracting party to claim your rights un...

Page 20: ...0 Hansgrohe Units D1 D2 Sandown Park Park Trading Estate Royal Mills Esher Surrey KT10 8BL Technical Hotline 01372465655 E Mail technical hansgrohe co uk Internet www hansgrohe co uk 07 2018 9 05577 0...

Reviews: