12
SW 3 mm
1
2
3
Thermostatic Adjustment
Temperature Limitation
The temperature is limited by the safety stop to 40°C.
If a higher temperature is required, it is possible to over
ride the safety stop by depressing the safety button.
NB.
It is recommended that for
private domestic
use
the maximum mixed water temperature be set at the
following factory set values:
Shower Mixer 43°C
Bath/Shower 46°C
Bath/Shower Mixer when installed as type 3 valve the
maximum mixed water temperature shall be set at 43°C
for both outlets (bath & shower)
Temperatures can be set by following the procedures
under
„Setting thermostat to a maximum tem-
perature“.
This ensures that after correct installation
the outlet temperature of the water can never exceed
43°C.
To guarantee a smooth running of the thermostatic
element, it is necessary from time to time to turn the ther-
mostat from total hot to total cold. The thermostatic mixer
valve should be checked annually by a qualified person
to ensure correct operation.
The mixer is fitted with check valves (page 17
#96644000) and filters (page 17 #96922000). If the
water flow drops the filters need to be cleaned. For that
purpose the mixer has to be removed from the wall.
Calibrating Thermostat
1. If the temperature reading is different to the
showering temperature, turn the thermostat
handle until a 40°C reading is shown on your ther-
mometer.
2. Remove the handle end cap, undo the screw (fig. 1).
3. Pull off the handle (fig. 2).
4. Remove the circlip from the spindle and slide off the
locking ring (fig. 3).