background image

                 

Operating Manual

                               

for HMG gasburner

Hansa burners are quality products. Expert installation, regulation/adjustment and servicing/maintenance
provided, our burners will work safely, reliably and economically for many years.

Before the assembly of the burner
the following steps have to be carried out:

Installation and Commissioning

This burner has to be installed and commissioned only by an expert. Therefore locally valid rules and
guidelines are to be strictly observed. He will bear responsibility for the appropriate laying out.

Norms

The following norms have to be considered for safe, environment-friendly and energy-saving running: 

DIN

4756

 gas firing units, DIN 4788 part 2 gas burner with fan ventilation, DIN 4789 connection of atomizing

oil- and gasburner with fan ventilation on heat generators, VDE 0116 elektrical equipment of firing plants.

- Check, whether the heat generator is impermeable on its smoke gas side.
- In case of second hand heat generators the heating surfaces have to be clean in order
  to achieve a good degree of effectiveness.
- Gas pipes have to be laid professionally and must be absolutely impermeable.

Content of box:

1 Gasburner HMG

           2  Fixing screws M8

1 Operating-Manual

     mit 2 underlay discs

1 Flange gasket

           1 Gasvalve

1 Plug with 7 poles

            1 Conic case fixing screw

Assembly:

First you take the burner out of its box and dismantle the burner's bonnet.
Then you loosen the 4 outer screws of the burner case and take the upper part out of the lower part.
Now you fix the lower part to the boiler by means of the flange gasket (pic.1). Fit the upper part to the
lower part again and tighten the four outer screws. Now you assemble the gas valve, the gasket of

which you will also find in the transparent pack. Finally
assemble the gas supply to the gas valve. If gas supply and
electrical connection (euro-plug with 7 poles) is established, the
burner is operational. Please pay attention to the remark relating
to the air blockade on page 5.

Picture1  flange gasket
LK=150
L = 81mm
F = 8,5

          page 2 of 5

Summary of Contents for HMG

Page 1: ...degascompl 8 Gasfeuerungsautomat Gasfiringautomat Boîterelaisgazautomatique CofredeSeguridadparaQ gasunit 3089 9 Motor 230V 50Hz 70W Engine230V 50Hz 70W Moteur230V 50Hz 70W Motor 230V 50Hz 70W 3434 10 Luftrad Fanwheel Ventilateur Ventilador 1675 11 Zündtransformator Ignitiontransformer Transformateur d allumage Transformadordeencendido 3174 12 Luftabschlußklappe air choke Voletd air Válvuladeaire ...

Page 2: ...second hand heat generators the heating surfaces have to be clean in order to achieve a good degree of effectiveness Gas pipes have to be laid professionally and must be absolutely impermeable Content of box 1 Gasburner HMG 2 Fixing screws M8 1Operating Manual mit 2 underlay discs 1 Flange gasket 1 Gasvalve 1 Plug with 7 poles 1 Conic case fixing screw Assembly First you take the burner out of its...

Page 3: ...3 7 3 6 3 6 3 5 3 4 3 3 3 2 3 1 3 0 2 9 2 8 32 0 27 5 35 6 4 2 4 1 4 0 3 9 3 8 3 7 3 6 3 5 3 4 3 3 3 2 3 1 36 0 31 8 40 0 4 8 4 6 4 5 4 4 4 3 4 2 4 1 3 9 3 8 3 7 3 6 3 5 40 0 34 4 44 4 5 3 5 2 5 0 4 9 4 8 4 6 4 5 4 4 4 3 4 1 4 0 3 9 45 0 38 7 50 0 6 0 5 8 5 7 5 5 5 4 5 2 5 1 4 9 4 8 4 6 4 5 4 3 50 0 43 0 55 6 6 6 6 5 6 3 6 1 6 0 5 8 5 6 5 5 5 3 5 1 5 0 4 8 Gasflowtable page 3 of 5 IMPORTANT Measur...

Page 4: ...Seite 4 von 5 Description and explanation of function of Dung s compact unit GB LEP 055D01 ...

Page 5: ...ththeaforementionedconditions faultyhandlingorwrongconnections theguaranteeexpires Electrical Connection Connecting of the 7 4 pole plug is done according to VDE 0116 and the electrical wiring diagram on page 5 Furthermore it is essential to take care of correct polarity of the Euro plugs connecting boiler and burner check of phasing If this instruction is not heeded this will automatically lead t...