background image

10

A100g 
JULY 2017

LED LOGIC

GAS SENSOR LED INDICATORS

LED OPERATIONS

RESULT

Green LED Flashing / Red LED off Warming up ≈ 5 min
Green LED on / Red LED off

Ready to detect gas

Green LED on / Red LED on

Gas level above gas 
sensor trip point

Green LED off / Red LED on

Sensor element 
failure or sensor 
disconnected

Green LED off / Red LED flashing

Low supply voltage or 
low supply current

TABLE 3

CALIBRATION PROCEDURES

Refer to Fig. 12 for calibration of Hansen sensors.

Equipment required:

Hansen calibration kit, stopwatch, hex wrench; 5/32˝, 
long nose pliers, 24V AC/DC power supply, voltmeter, 
2 minigrabber voltmeter leads and calibration gas for 
the specific sensor.

Setup:

1.   B e   s u r e   t h e   s y s t e m   i s   m a d e   s a f e   d u r i n g 

calibration. The 4-20mA output and internal relay 

will be active during calibration.

2.   Be sure the gas sensor has been powered up for a 

minimum 24 hours to stabilize the sensing element.

3.   Verify the green LED is illuminated and the red LED 

is off. 

4.   Disable the internal horn by removing JP2 jumper.

Zero Calibration:

5.   Set the voltmeter to the appropriate DC range. The 

sensor element output is measured in DC volts; 

zero volts equals zero PPM and 5 volts equals the 

gas sensor PPM rating. (i.e. 100 PPM, 250 PPM). 

Attach the voltmeter leads to the VS, (+) lead from 

the voltmeter, V0, (-) lead of the voltmeter. 

6.   Be sure the ambient atmosphere around the gas 

sensor is free of any background gases. To zero 

CO2 sensors, pure nitrogen needs to be used to 

ensure free ambient conditions.

7.   Adjust the zero potentiometer (Z) until the voltage 

reading on the voltmeter reads between zero volts 

and +/- 0.030VDC.

Span Calibration:

1.   Always perform the zero calibration before doing 

the span calibration.

2.   Place the boot over the sensor element. Use the 

correct concentration of calibration gas for the 

full range of the sensor. In other words, for a gas 

sensor with a range of 0 to 250 PPM, use a 250 PPM 

calibration gas when setting the span. If full range 

calibration gas is not available, a calibration gas of 
less than full range can be used then adjust to the 
corresponding output voltage. This may result in 
some loss of accuracy. 

3a. 

G a s   s e n s o r s   ( e x c e p t   V e n t   l i n e   a n d 
S e m i - c o n d u c t o r   g a s   s e n s o r s ) .

 

Start the flow of gas. Observe the output, it should 
begin to increase after 5 seconds. Leave the gas 
flow on and observe the voltage. The sensor voltage 
will slowly climb toward 5VDC. When the voltage 
does not change by more than +/- 0.010 volts per 15 
seconds the sensor output voltage is considered to 
be stable. Adjust the span potentiometer (S) so the 
output voltage reads between 4.95 to 5.00 volts DC. 

3b. 

 Vent line and Semi-conductor gas sensors

  

Start the flow of gas. Observe the output, it should 
begin to increase after 5 seconds. Leave the gas 
flow on and observe the voltage. The sensor voltage 
will ramp up quickly. When the voltage does not 
change by more than +/- 0.010 volts per 15 seconds 
the sensor output is considered to be stable. Adjust 
the span potentiometer (S) so the output voltage 
reads between 4.95 to 5.00 volts DC.

4.   Stop the flow of gas and remove the boot from the 

sensor element. Verify the sensor voltage output 
begins to decrease.

5.  Do not attempt to re-adjust the zero or span 

calibration until another 24 hours of powered 
operation has passed. 

6.   Enable system. Verify proper operation. 
7.   Enable the internal horn by installing JP2 jumper.

Electrochemical Sensor Only (Zero Offset)

If the gas sensor is calibrated in the environment for 
which it will be used a final zero adjustment will not be 
necessary. If the gas sensor will be calibrated at one 
temperature (70ºF, 21ºC) then moved to its operating 
environment (-4ºF, -20ºC) a maximum zero offset of 
2% will occur. If unacceptable, adjust the zero point as 
described in section 

Calibration Procedures, Zero 

Calibration

. At (-40ºF, -40ºC), a maximum zero offset 

of 12% will occur. If unacceptable, adjust the zero point 
as described in section 

Calibration Procedures, Zero 

Calibration

.

CALIBRATION GAS CYLINDERS

Warning: Refer to Material Safety Sheet supplied with 
gas cylinder and local safety precautions for proper 
usage, handling and disposal.

Hansen calibration gas standards are traceable to NIST 
(National Institute of Standards and Technology) and 
analysis data is available on request.

A variety of calibration refrigerant gases and PPM ranges 
are available, refer to Page 23. For special mixtures, 
consult factory. Calibration gas should be stored in a 
cool area, 65ºF/75ºF. Shelf life labeled on cylinder−one 
year from date of manufacture.

Calibration gas must be shipped according to Department 
of Transportation Hazardous Gas Regulations. Special 
shipping charges will apply. Shipping only available in 
the continental USA. 

Summary of Contents for HSC4H-N10K

Page 1: ...urrounding environment The analog outputs 4 20mA or 0 10V DC can interface with nearly any existing monitor computer or PLC controller The sensing elements except Basic and Extreme Gas Sensors are mou...

Page 2: ...ors or outdoors Enclosure is NEMA4X IP65 conduit connection must be vaporproof Note Auxilliary power required when used with Hansen monitors HLM2 and HLM6 and Gas Alert System Vent Line Gas Sensor For...

Page 3: ...mount the gas sensor below the coil to avoid high moisture and steam during defrost The two generally accepted methods of locating sensors are Point and Perimeter detection Point detection is where se...

Page 4: ...LOOP RESISTANCE 1000 OHMS OUTPUT 4 20mA 0 5V 1 5V 0 10V 2 10V DC 4 20mA SIGNAL OUTPUT Isolated 2 wire ALARM RELAY SPDT 1 A 120V TRUE ALTITUDE 2000M POLLUTION DEGREE 2 4 EQUIPMENT CLASS 3 INSTALLATION...

Page 5: ...ALARM SIMPLE ALARM SYSTEM INDOOR OUTDOOR VISUAL ALARM AUDIBLE ALARM GAS SENSOR INSIDE SPACE OUTSIDE SPACE GAS SENSOR ELEMENT 10 3m CABLE MAX WEATHER PROOF GAS SENSOR ELECTRONICS RELIEF LINE DISCHARGE...

Page 6: ...tage signal wires be in a common conduit tray or wiring panel with power wiring over 48 volts Do not run wires near variable frequency drive VFD equipment When using the gas sensors connected directly...

Page 7: ...SHIELD AT OTHER END Voltage Selector D 24V DC A 24V AC D A Fail Safe Relay Relay engerized to normally open position when power applied AC APPLIED VOLTAGE POWER SEMI CONDUCTOR SENSOR NO NC COM V V 0 V...

Page 8: ...8 A100g JULY 2017 INFRARED SENSOR SHOWN WIRED FOR 4 20MA OUTPUT FIG 11...

Page 9: ...SOR OPERATION On power up the internal relay will energize switching from the normally closed position to the normally open position In addition the sensor will go through an initial warm up delay for...

Page 10: ...e output it should begin to increase after 5 seconds Leave the gas flow on and observe the voltage The sensor voltage will slowly climb toward 5VDC When the voltage does not change by more than 0 010...

Page 11: ...oof Sensing Elements are externally mounted to the enclosure To replace disconnect power open enclosure and disconnect cable wire from the circuit board Unscrew sensor element from enclosure Install n...

Page 12: ...relays alarms 10 amp 230V AC 1 SPDT dry contact relay fault output 10 amp 230V AC HLM6 Model only Power Required 100 230 VAC Power Consumption HLM2 15W HLM6 25W Audible Alarm HLM2 internal 80 dB HLM6...

Page 13: ...ge across VHIGH and GND Set the desired high level alarm relay using VHIGH Pot which is located furthest from the calibration pins This setting applies to the six channels SETTING ALARM OUTPUT FOR HLM...

Page 14: ...14 A100g JULY 2017 HLM2 WIRING DIAGRAM FIG 13...

Page 15: ...15 A100g JULY 2017 HLM6 WIRING DIAGRAM FIG 14...

Page 16: ...m sensor fault Symptom Output from sensor is 2mA for 4 20mA output Output from sensor is 0 V or 5V for 0 10 0 5 1 10 1 5 output signals Cause 1 Sensing element has failed or is disconnected from print...

Page 17: ...6 5 94 151 2 56 65 62 16 2 07 53 4 13 105 173 DIA 4 4 MOUNTING HOLE 3 PLACES 29 7 2 93 78 6 37 162 358 DIA 9 1 MOUNTING HOLE 3 10 79 7 58 191 173 DIA 4 4 MOUNTING HOLE 3 PLACES 358 DIA 9 1 MOUNTING HO...

Page 18: ...monitored system or as part of a larger gas monitoring and signaling system The lower cover to the terminal compartment must be removed to gain access for wiring Knockouts are available for and condui...

Page 19: ...REEN RED REMOTE SENSOR V V V I NO COM NC 0 0 V V V I COM CONTROL 0 RELAY NC RELAY COM SIGNAL POWER COM SHIELD SIGNAL POWER POWER SHIELD ppm Power Supply 24V AC DC EARTH GRD Multi Wire Cable Shield JUM...

Page 20: ...4 PT ANALOG IN MODULE CURRENT GREEN RED V V V I NO COM NC 0 0 V Power Supply 24V AC DC EARTH GRD Multi Wire Cable Shield REMOTE SENSOR INPUT 1 INPUT 2 INPUT 3 INPUT 4 ANALOG GND REMOTE SENSOR REMOTE...

Page 21: ...21 A100g JULY 2017 TYPICAL WIRING DIAGRAM WITH LOCAL POWER SOURCE FIG 22...

Page 22: ...nnected to relay _______________________________ OK Check Analog Output in Use e g 0 5V 4 20 mA _______________________________ OK 2 On Site Gas Calibration Initial the following encircle OK when comp...

Page 23: ...4E F3K R410 Semiconductor 0 3 000 Note Gas Sensors available for additional refrigerants consult factory TABLE 9 CO2 Sensor Type Range PPM Basic to 32 F 0 C Harsh to 40 F 40 C Extreme to 60 F 50 C HIR...

Page 24: ...conductor 31 1025 Harsh Extreme Ammonia 100 250 Electrochemical 31 1005 Harsh Extreme Ammonia 1000 Electrochemical 31 1006 Harsh Extreme Ammonia 10 000 Semiconductor 31 1007 Vent Line Ammonia 10 000 S...

Reviews: