BS03 fixed gas detector operation manual 

 

Working method: Continuous monitoring 
Accuracy: ≤±5%F.S. 
Indication method: 4-digit LED light 
Condition display: 3 LED lights indicate fault alarm, L-alarm and H-alarm 
Operation: Infrared remote control 
Response time: ≤30s (LEL) / ≤60s (toxic gas) 
Working temperature: -40

℃~

70

  (LEL) / -20

℃~

50

  (toxic)   

Working humidity: 

95%RH 

Explosion-proof: Ex d

CT6 

Protection: IP65 
Pressure Limit: 86-106kPa 
Signal output: 4

20mA    or RS485, 2 relay output 

Install screw thread: G3/4" 
Cable dimension: ≥1.5mm

2

×3 

Transmission distance: ≤1000m 
Dimensions: l×b×h, 210×200×105mm 
Weight: about 2100g

 

 

3

Structure 

 

Summary of Contents for BS03

Page 1: ...BS03 Fixed gas detector Operation manual Read this manual carefully before using the device Ver HWWM160617CG...

Page 2: ...wise it will influence the accuracy and shorten the sensor life 8 Please don t paint the sensor parts or detector 9 Only sensor spare parts which are specified for BS03 are allowed to be used 10 It s...

Page 3: ...ION 3 4 1 INSTALLATION POSITION 3 4 2 DIMENSIONS 4 4 3 INSTALLATION METHODS 4 5 WIRE CONNECTION 6 6 OPERATION 8 6 1 LOW ALARM SETTING 9 6 2 HIGH ALARM SETTING 9 6 3 ZERO TRANSLATION 9 6 4 SINGLE POINT...

Page 4: ...n Gas Range Resolution Calibrating gas flow LEL 0 100 LEL 1 LEL 500 50ml min CH4 C3H8 0 100 LEL 1 LEL 500 50ml min CH4 0 5 VOL 0 1 VOL 500 50ml min CO 0 1000PPM 1PPM 200ml min H2S 0 100PPM 1PPM 200ml...

Page 5: ...H alarm Operation Infrared remote control Response time 30s LEL 60s toxic gas Working temperature 40 70 LEL 20 50 toxic Working humidity 95 RH Explosion proof Ex d CT6 Protection IP65 Pressure Limit 8...

Page 6: ...thin 1m around the possible gas leakage area such as valve pipe connection point gas outlet place Please try to install it nearer to the above places but avoid influencing the working of the other equ...

Page 7: ...ace you can fix the detector onto the wall or to the gas pipes Please follow the details as below Method 1 thread butted type fixing method If there are transverse or vertical siphon with G3 4 Screw t...

Page 8: ...thod 2 If the user needs to install the detector onto the wall please choose an appropriate place on the wall according to the detector dimensions Then fix the detector by using 3 pieces of M6 70 bulg...

Page 9: ...e way Then use a cross type screw to screw down the 3 bolts and take off the display PCB 2 Screw down the pipe connector in counter clockwise way Take out the explosion proof pad In turns put 3 line w...

Page 10: ...NO mark function spec 1 L Alarm Low alarm output Switching value 2 L Alarm Low alarm output 3 24V Power input DC24V 25 4 GND Power input 5 Iout Current ouput 4 20mA 6 NC 7 H Alarm High alarm output S...

Page 11: ...firm Cancel and Warning It s forbidden to replace the batteries for the remote control in working area Note Setup Confirm and Cancel are single spring buttons These buttons can only be triggered once...

Page 12: ...to exit to return to the normal status 6 2 High alarm setting In normal status press Setup twice and it displays F 2 Then press Confirm it displays the default high alarm This figure can be adjusted b...

Page 13: ...working status the screen will show F 4 then press Confirm and it will display the default calibration point Press or to change the calibration point to be same with the input gas concentration level...

Page 14: ...ent catalytic sensor s using life is 3 years electrochemical sensor s using life is 2 years When the sensor life is overdue the detection result may be not accurate To replace the sensor please first...

Page 15: ...BS03 fixed gas detector operation manual 12...

Page 16: ...Electrical fault Contact with seller Abnormal connection with controller Wiring fault Check the wiring Electrical fault Contact with seller E 01 Calibration fault recalibrating E 02 Wiring fault conn...