background image

4

5

6

Power supply P3 : 10 - 24 V d.c/a.c,  50 - 60 Hz

P4 : 100 - 240  V a.c,  50 - 60 Hz

Power consumption

5.5 VA

Input

K, Pt100 Ω, 4 - 20 

 d.c, 1 - 5 V d.c

Display accuracy ± 0.5 % of F.S ±1 Digit

Control output 

Relay  Contact composition : 1 c, 250 V a.c, 

 5 A (resistive load)

S.S.R Approx. 5 V d.c (resistive load min 500 Ω), 

Approx. 50 mA max

Alarm & defrost

Relay  Contact composition : 1 c, 250 V a.c, 

 5 A (resistive load)

Control operation Two Position Operation (ON/OFF)  

Proportional Operation (P)

Setting method Digital method by setting, up and down keys

Other functions Auxiliary output(Alarm & Defrosting Timer) Heating/

cooling

Resistance 

between wires

Thermocouple  Below 100 Ω for each wire

R.T.D

Below 10 Ω for each wire

(Resistance of 3 wires should be the same.)

Operating ambient

temperature/humidity 0 ~ 50 ℃/ below 35 ~ 85 % R.H (With no condensation)

Model

Code

Description

ED6 -

☐ ☐ ☐ ☐ ☐

Digital Temperature Controller

Control 

type

F

ON/OFF Control

P

Proportional control

Input

K

Thermocouple (K Type)

P

R.T.D Pt100 Ω (IEC)

C

4 - 20 

 d.c (attach 250 Ω of external 

resistance), 1 - 5 V d.c

Control output

M

Relay

S

S.S.R (Voltage pulse output 5 V d.c)

Optional

A

Alarm or defrosting timer

N

NONE

Power supply voltage

P3 10 - 24 V d.c/a.c,  50 - 60 Hz
P4 100 - 240  V a.c,  50 - 60 Hz

  Digital Temperature Controller

 

ED6 

       Thank you for purchasing HANYOUNG product.

       Please check whether the product is the exactly same as you ordered. 

       Before using the product, please read this instruction manual carefully.

       Please keep this manual where you can view at any time

 INSTRUCTION MANUAL

Safety information

DANGER indicates an imminently hazardous situation 

which, if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation 

which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, 

if not avoided, may result in minor or moderate injury

Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality

DANGER

WARNING

CAUTION

There is a danger of occurring electric shock in the input/output terminals so 

please never let your body or conductive substance is touched.

•  If the user use the product with methods other than specified by the 

manufacturer, there may be bodily injuries or property damages.

•  If there is a possibility of an accident caused by errors or malfunctions of this 

product, install external protection circuit to prevent the accident.

•  To prevent defection or malfunction of this product, apply a proper power 

voltage in accordance with the rating.

•  Since this product is not designed with explosion-protective structure, do 

not use it any place with flammable or explosive gas.

•  Reassemble this product while the power is OFF. Otherwise, it may be a 

cause of malfunction or electric shock.

•  There is a possibility of occurring electric shock so please use this product 

after installing it to a panel while it is operating.

•  Before using a temperature controller, there could be a temperature 

difference between PV of the temperature controller and the actual 

temperature  so  please  operate  the  temperature  controller  after 

compensating the temperature difference appropriately.

•  The contents of this manual may be changed without prior notification.

•  Make sure that there is no damage or abnormality of the product during 

delivery.

•  Do not use this product at any place with direct vibration or impact.

•  Do not use this product at any place with liquid, oil, medical substances, 

dust, salt or iron contents.(Use at Pollution level 1 or 2)

•  Do not use this product at any place with a large inductive difficulty or 

occurring static electricity or magnetic noise.

•  In case of inputting thermocouple, use a compensating cable. (If using a 

normal wire, there is a possibility of occurring temperature error.)

•  For R.T.D input, use a cable which is a lead wire has small resistance and 

resistances of three wires shall be the same. (If the three wires have 

different resistances then there will be a temperature error.)

•  Separate an input signal cable from an output signal cable. If separating is 

not possible, please use the input signal cable after shielding it.

•  Use non-earth sensor with thermocouple. (In case of using earth sensor, 

there is a possibility of occurring malfunction caused by a short circuit.)

•  If there is excessive noise from the power supply, using insulating 

transformer or noise filter is recommended. The noise filter must be 

attached to a panel which is already connected to a ground and the wire 

between the filter output and power supply terminal must be short as 

possible.

•  When attaching this product to a panel, use an approved switch or circuit 

breaker from IEC947-1 or IEC947-3.

•  The warranty period for this product including parts is one year if this 

product is properly used.  

•  When the power is on, the preparation period of contact output is required. 

In case of using for signals of external interlock circuit, use with a delay 

relay.

DANGER

WARNING

CAUTION

Suffix Code

Specification

MA0602KE120813

1381-3, Juan-Dong, Nam-Gu Incheon, Korea.  
TEL:(82-32)876-4697
FAX:(82-32)876-4696  
http://www.hynux.net

Jl. cempaka blok F16, No.02 Delta Silicon II  
Cikarang Bekasi Indonesia
TEL : 62-21-8911-8120~4
FAX : 62-21-8911-8126 

HANYOUNGNUX CO.,LTD

PT. HANYOUNG ELECTRONIC INDONESIA

HEAD OFFICE

INDONESIA

FACTORY