Please read the safety information carefully then use the product correctly.

The alerts declared in the manual are classified into 

Danger

Warning

 and 

Caution

 

according to their importance

▍Safety information

28, Gilpa-ro 71beon-gil, 

Michuhol-gu, Incheon, Korea

TEL : +82-32-876-4697 

http://www.hynux.com

HANYOUNGNUXCO.,LTD

Non-indicating type temperature controller

ND4 

Thank you for purchasing Hanyoung Nux products. 

Please read the instruction manual 

carefully before using this product, and use the product correctly. 

Also, please keep this instruction manual where you can see it any time. 

MA1104KE191111

MA1104KE191111

INSTRUCTION MANUAL

   

DANGER

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

   

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

   

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or property damage

• Since this product is not equipped with a power switch and fuse, install them separately on the outside. 

  (fuse rating: 250Va.c. 0.5Aa.c.)

• Please supply the rated power voltage, in order to prevent product breakdowns or malfunctions.

• To prevent electric shocks and malfunctions, do not supply the power until the wiring is completed.

• The product does not have an explosion-proof structure, so avoid using it in places with flammable or explosive gases.

• Never disassemble, modify, process, improve or repair this product, as it may cause abnormal operations, electric shocks or fires.

• Please disassemble the product after turning OFF the power. Failure to do so may result in electric shocks, product abnormal 

  operations or malfunctions.

• Please use this product after installing it to a panel, because there is a risk of electric shock.

• The contents of this manual may be changed without prior notification.

• Before using the product you purchased, make sure that it is exactly what you ordered.

• Make sure that there is no damage or abnormality of the product during the delivery.

• Please do not use it in case of the time setting is 0. It may be a cause of its malfunction.

• Please turn the power off before changing the time setting. In case of changing the time setting while it is ON, please reset it.

• Please use the product in places where corrosive gases (especially harmful gases, ammonia, etc.) and flammable gases are 

  not generated.

• Do not use this product at any place with direct vibration or impact.

• Do not use this product at any place with liquid, oil, medical substances, dust, salt or iron contents. (Use at Pollution level 1 or 2)

• Do not polish this product with substances such as alcohol or benzene. (Use neutral detergent.)

• Do not use this product at any place with a large inductive difficulty or occurring static electricity or magnetic noise.

• Do not use this product at any place with possible thermal accumulation due to direct sunlight or heat radiation.

• Install this product at place under 2,000m in altitude.

• When water enters, short circuit or fire may occur, so please inspect the product carefully.

• If there is excessive noise from the power supply, using insulating transformer and noise filter is recommended. The noise 

  filter must be attached to be a panel grounded, and the wire between the filter output side and power supply terminal

  must be as short as possible.

• If putting the power cables closely together then it is effective against noise.

• Do not wire anything to unused terminals.

• After checking the polarity of terminal, connect wires at the correct position.

• When you install this product to a panel, please use switches or circuit breakers compliant with IEC60947-1 or IEC60947-3.

• Please install switches or circuit breakers at close distance for user convenience.

• Write down on a label that if the circuit breaker or switch is operating then the power will be disconnected since the circuit 

  breaker or switch is installed.

• For the continuous and safe use of this product, the periodical maintenance is recommended.

• Some parts of this product have limited life span, and others are changed by their usage.

• The warranty period for this product including parts is one year if this product is properly used.

• When the power is on, the preparation period of contact output is required. In case of using signals of external interlock 

  circuit or etc., use it with a delay relay.

• The input/output terminals are subject to electric shock risk. 

  Never let the input/output terminals come in contact with your body or conductive substances.

DANGER

WARNING

CAUTION

▍Specification

▍Suffix code

Model

Code

Content

ND4 -

□ Non-indicating type temperature controller

Control type

F

ON/OFF control (2 position control)

P

Proportional control

Input

K

K thermocouple

P

RTD Pt100 Ω (IEC)

Control output

M

Relay

Control operation

R

Reverse control (Heating control)

D

Direct control (Cooling control)

Range code

Select the standard range code

Terminal structure

T

Terminal type

※ Specify the power voltage of ND4 separately either. 110Va.c. or 220Va.c.

Power supply voltage

110/220Va.c. 60Hz

Voltage variation rate

± 10% of supply voltage

Power Consumption

3 VA

Input

Thermocouple, RTD (Pt100 Ω)

Adjusting Sensitivity

0.2% (fixed) of Max. Range

Control Method

Proportional control, ON/OFF control

Setting Method

Analog setting

Control output

·Relay Output : 250Va.c. 3 A (Resistive Load) SPDT

·SSR Output : Voltage pulse 12Vd.c. (Resistive Load Min.800 Ω)

Setting Accuracy

Same as display value without relative error

Proportional Band

3% of FS (fixed)

Relay Life Expectancy

·Mechanical : Min.10 millions times.

·Electrical : Min. 100 thousands times. (250Va.c. 5 A Resistive Load)

Sampling Cycle

·Relay Output : 20 sec       ·SSR Output : 2 sec

External Input Resistance

·Thermocouple: Max. 100Ω

·RTD: Max. 10Ω per 1 wire (the resistance of each wire should be the same.)

Dielectric strength

2000Va.c. 60Hz for 1min

Ambient Temperature · Humidity

0 - 50 ℃, 35 ~ 85% RH (Without condensation)

Vibration 

resistance

Durability

2 - 55 Hz, X·Y·Z in each direction for 10 min

Malfunction

10 - 55 Hz, 0.76 mm, X·Y·Z in each direction for 2 min

Shock resist

Durability

300 ㎧²

Malfunction

200 ㎧² 

Weight (g)

Approx. 220 (including installation adaptor)

▍Standard Range

Code

Input

Temperature range (℃)

Code

Input

Temperature range (℃)

1

Pt

-50 ~ 50

5

Pt, K

0 ~ 200

2

Pt

-100 ~ 100

6

Pt, K

0 ~ 300

3

Pt

0 ~ 100

7

Pt, K

0 ~ 400

▍Connection diagram

▍Dimensions and panel cutout

▍Function descriptions

※ Control method is determined by product code when ordered.

Proportional control is that an output capacity regarding a setting value (SV) is proportionally operated by a deviation. The 

width which the output is varied within 0 ~ 100% is called proportional Band (PB). Therefore, for reverse action, if 

PT=Present (Process) temperature.

PT < PB → Output capacity 100%

PT > PB → Output capacity 0%

PT = PB → Output capacity 50%

This is a control method that if PT is higher than SV then output will be OFF or if PT is less than SV, then the output will be ON. 

Also, it is called 2-position control since it outputs either 0% or 100%. The status which the temperature is unstable and there is 

high/low wave around SV is called hunting. The width between the point where its output is OFF because PT is higher than SV 

and the point where its output is ON since PT is less than SV is called adjusting sensitivity, hysteresis. If the width, hysteresis, is 

narrow, then high/low wave becomes smaller but the cycle of ON-OFF gets smaller so that it may severely damage to 

electromagnetic switch, electrovalve or etc.. Especially, for controlling burner which is using freezer or electrovalve, 2-postion 

control is generally used.

■ Proportional control

■ 2-position Control, ON-OFF Control

[Unit:mm]

※ The power voltage of ND4 is divided into 220Va.c. 60Hz or 110Va.c. 60Hz when ordered. Make sure to check and

       turn on the power voltage.

■ Terminal Type

■ Socket Type

7BD7BD

)[

7BD"

7BD7BD

)[

7BD7BD

)[

7BD"

7BD7BD

)[

■ Panel cutout

※ Socket type and terminal type panel cutouts are the same.

■ Terminal Type

■ Socket Type

5JNF

5FNQFSBUVSF

4FUUJOH7BMVF

0WFSTIPPU

)VOUJOH "EKVTUJOH4FOTJUJWJUZ

0VUQVU

5FNQFSBUVSF

4FUUJOH7BMVF

1SPQPSUJPOBM#BOE

1SFTFOU5FNQFSBUVSF

5JNF

1SPQPSUJPOBM#BOE

4FUUJOH7BMVF

5JNF

5FNQFSBUVSF

4FUUJOH7BMVF

0WFSTIPPU

)VOUJOH "EKVTUJOH4FOTJUJWJUZ

0VUQVU

5FNQFSBUVSF

4FUUJOH7BMVF

1SPQPSUJPOBM#BOE

1SFTFOU5FNQFSBUVSF

5JNF

1SPQPSUJPOBM#BOE

4FUUJOH7BMVF

All manuals and user guides at all-guides.com

all-guides.com

Reviews: