25
8-4. Setup Menu (STUP)
●
Communication Group (G.COMM)
●
Output Group (G.OUT)
Menu
Code
Parameter
Setting Range
Display
Condition
Default
Value
PWD
Password
0 ~ 9999
PWD.C
0
PR-S
RS485, RS422
Protocol select
PC-LINK / PC-LK-S
/ MODBUS ASCII / MODBUS RTU
OPT
PC-LINK
BPS
Baud Rate
600 - 38400
9600
PRI
Parity
NONE / EVEN / ODD
NONE
STP
Stop Bit
1, 2
1
DLN
Data Length
7, 8 (Except PC-LIN : 8)
8
ADR
Address
1 ~ 99
1
RP.T
Response Time
0 ~ 10
0
Menu Code
Parameter
Setting Range
Display Condition
Default Value
PWD
Password
0~9999
PWD.C
0
OUT
Output Type
Please refer output type
Always
Universal : Relay
Heating/Cooling :
SSR/SSR
O.ACT Output Action
REVERSE
DIRECT
Universal
REVERSE
HCT
Heat cycle Time
1 ~ 1000 s
RLY or SSR Output
(Except ON/OFF
control)
RLY : 30 s
SSR : 2 s
CCT
Cool cycle Time
1 ~ 1000 s
Heating/Cooling RLY
or
SSR output
RLY : 30 s
SSR : 2 S
HYS
〔Hysteresis
(ON / OFF Control)〕
EUS (0 ~ 100 %)
ON/OFF control
EUS (0.5 %)
Heating, Cooling, Normal 0.0 ~ 100.0 %
Heating/Cooling
0.5 %
HEO
Heat Emergency output
Preset Out 1, (Heat)
-5.0 ~ 105.0 %
Heating/Cooling : 0.0 ~ 105.0 %
Always
0.0 %
CEO
Preset Out 2
Cool Emergency output
0.0 ~ 105.0 %
Heating/Cooling
0.0 %
OL-H
Output Limit High
OL-L + 1digit ~ 105. %
Heating/Cooling: 0.0 ~ 105.0 %
PID
100.0 %
OL-L
Output Limit Low
-0.5 % ~ OL-H - 1digit
Heating/Cooling: 0.0 ~ 105.0 %
PID
0.0 %
HC : 100.0 %
Caution
After setting Input group, Output group, please setup other groups.
Summary of Contents for NP200