Burn-Out Detection
●
PV Limiter
●
PV during the A/D Error
●
Reference Conjunction Compensation (RJC)
The Burn-Out (B.OUT) function determines the control outputs including PV up/or down scale, retransmission output and Alarm
when an input disconnection/failure occurs (such as sensor). The Burn-Out is used in the input range of Thermocouple and RTD.
•When the Burn-Out is detected (B.OUT=UP, DOWN), the retransmission and alarm operation is affected and a Control
Output is the Preset-Out.
•When the Burn-Out is not detected (B.OUT=OFF), the PV is rejected and a Control Output is normal (No Preset-Out occurs).
•-OVR or OVR presents on PV Display when the PV is in either -5% or 105% of the input range.
(a controller runs as per either -5% or 105% of PV)
• PV > EU (105 %): PV=105 %, PV Display= OVR
• EU(-5 %) ≤ PV ≤ EU(105 %): PV= PV
• PV < EU (-5 %): PV= -5 %, PV Display=-OVR
•The error message presents on PV Display when an A/D error occurs.
•A controller runs an alarm and retransmission operations as per 105% of PV.
● Lock Functions
Key, Menu, and Password locking prevents the accidental or unauthorized change.
•The reference conjunction compensation is automatically performed when the input type is a Thermocouple.
•When the RJC error occurs, the error message and PV presents on PV Display and a controller runs as per RJC=0 ℃.
B.OUT (Burn-Out)
UP (Up Scale)
DOWN (Down Scale)
OFF (OFF)
Thermocouple/RTD
(DC, V, mV is invalid)
Detection
◯
◯
X
PV
105 %
–5 %
Rejected
Remark
RTD is +105% temporarily.
Up, Down or OFF
◼
Lock Group (G.LOCK)
Function
Code
Parameter
Description
KEY LOCK
PWD
Password
Access is denied if password entry is incorrect.
▽/△
Down Up Key Lock
DOWN & UP key is locked and PARAMETER EDIT is disabled.
PT.NO
Pattern Number Lock
PT.NO UP and PT.NO DOWN key are locked and PTN NO.
EDIT is disabled.
RUN
Run Key Lock
RUN/HOLD key is locked and PROG RUN is disabled.
A/M
Auto / Man Lock
Display-5 (Output Mode Display) is disabled. Shifting between
AUTO and MAN Mode is disabled.
Menu
PROG
PROG Menu Lock
PROG Menu is disabled.
OPER
OPER Menu Lock
OPER Menu is disabled.
FUNC
FUNC Menu Lock
FUNC Menu is disabled.
PASSWORD
(set-up)
PWD.C
Password Chage
Access to SETUP Menu is denied if password entry is incorrect.
P.INIT
Parameter Initialize
Pattern is initialized.