background image

3

•   Since the product operating environment influences the product performance and  expected life span, 

please avoid using in the following places.

  · a place where humidity is high and air flow is inappropriate.

  ·  a place where dust or impurity accumulates, ambient temperature is high and vibration level is high.

  ·  a place where corrosive gas (such as harmful gas, ammonia, etc.) and flammable gas occur.

  · a place where there is direct vibration and a large physical impact to the product.

  ·  a place where there is water, oil, chemicals, steam, dust, salt, iron or others (Contamination class 1 or 2).

  ·  a place where excessive amounts of inductive interference and electrostatic and magnetic noise occur.

  · a place where heat accumulation occurs due to direct sunlight or radiant heat.

•  Please do not wipe this product with organic solvents such as alcohol, benzene and others.

  (Please use mild detergent)

•  Please make sure to inspect the product if exposed to water since there is a possibility 

  of electric leakage or a risk of fire.

•  Please connect the product and other units after turning off all the power of the product, 

  instruments and units.

• Please make sure that the power control (TPR) is installed perpendicularly.

•  Please install the product inside of the control panel and install an exhaust fan onto the top of the

  control panel.

• Pay attention to the edge of heat sink which is sharp. 

Specification

Model

TPR-3M25L

TPR-3M45L

TPR-3M55L

Load voltage

90 - 240 V a.c.

Circuit operating power

24 V d.c. 8 W

Power frequency

50 / 60 Hz

Rated current

25 A

45 A

55 A

Applying load

Resistive load

Control Input

4 - 20 ㎃ d.c. (Impedance : 100 Ω)

Control method

Phase control (Fixed Cycle control, Variable Cycle control 

Option)

Output voltage

More than 98 % of the power supply voltage 

(In case of maximum current input)

Cooling method

Forced cooling (24 V d.c. FAN)

Display method

4 LED display status and alarm status

Insulation resistance

Min 100 MΩ (Base on 500 V d.c. mega)

Dielectric strength

2,500 V a.c. 50 / 60 Hz for 1 min

Line noise

Noise by noise simulator (2,000 V)

Storage temperature

-30 ~ 90 ℃

Ambient temperature

-20 ~ 80 ℃ (Without Condensation)

Ambient Humidity

45 ~ 85 % RH

Approval

Weight

1,756 g

MB0801KE230515

Part name and function

█ LED indicator and description

LED

Status

Alarm

Description

POWER

Flashing

When 4 - 20 mA control input is applied

Light on

When 24 V d.c. power is applied separately

EMG

Flashing Over current (Alarm2)

Over 55 A over current

Light on Power failure (Alarm2)

During operation (output is going out) 

when load power applied to 

TPR is cut off

HB

Flashing Load imbalance 

(Alarm2)

When the deviation of the maximum and 

minimum values of load connected to 

U, V, W is more than 10 A

Light on SCR error (Alarm1)

When the input current is 0 % (4 mA).

OT

Flashing Heat sink overheated 

60 ℃ (Alarm2)

When the heat sink temperature is 

above 60 ℃

Light on Heat sink overheated 

80 ℃ (Alarm1)

When the heat sink temperature is 

above 80 ℃

█ Explanation for alarm output

Alarm

TPR status

Alarm output

Alarm1 Forced shutdown 

(alarm output, LED display)

NPN transistor open 

collector output

(High signal at abnormal detection)

Alarm2 Normal operation 

(alarm output, LED display)

Thyristor Power Regulator

MADE IN KOREA

LOAD : 100 - 240 V

~

Maximum rated current : 25A

TPR-3M25L

POWER

EMG

HB

OT

Thyristor Power Regulator

MADE IN KOREA

LOAD : 100 - 240 V

~

Maximum rated current : 25A

TPR-3M25L

POWER

EMG

HB

OT

Suffix code

Model

Code

Information

TPR-3M

 □ □  -□ Slim 3-phase miniature power regulator

Load current

25

25 A

45

45 A

55

55 A (Made-to-order, inquire for pricing)

Load voltage

L

90 - 240 V a.c. (Low)

Option

IS Power isolated type

※ Option IS type is a product that can connect up to 5 in series with one temperature 

     controller and power supply (SMPS).  The general type requires a 1 to 1 connection to 

the temperature controller with a 24 V d.c. partial power circuit as a non-isolated type.

  Power REGULATOR

 

TPR-3M

      

 

         Thank you for purchasing HANYOUNG product.

         Please check whether the product is the exactly same as you ordered. 

         Before using the product, please read this instruction manual carefully.

         Please keep this manual where you can view at any time 

 INSTRUCTION MANUAL

Safety information

Before using the product, please read the safety information thoroughly and use it properly.Alerts 

declared in the manual are classified to Danger, Warning and Caution by their criticality

DANGER

DANGER indicates an imminently hazardous situation which, 

if not avoided, will result in death or serious injury

WARNING

WARNING indicates a potentially hazardous situation which, 

if not avoided, could result in death or serious injury

CAUTION

CAUTION indicates a potentially hazardous situation which, 

if not avoided, may result in minor or moderate injury

•  To prevent electric shock while it is running, put to earth with the fixed screw of the unit   and 

do not touch the radiator panel since it is very hot. 

• Do not touch or contact the input/output terminals because they cause electric shock.

Danger

•  Please install appropriate protective circuit on the outside if malfunction or an 

  incorrect operation may be a cause of leading to a serious accident.

•  If you use the product with methods other than specified by the manufacturer, 

  there may be  bodily injuries or property damages.

•  Since this product is not designed as a safety device if it is used with systems, 

  machines and equipment that could lead to a risk of life or property damage, 

  please implement safety devices and protections for both lives and the 

  applications and plan for preventing accidents. 

• To prevent damage or failure of this product, please supply the rated power voltage.

•  To prevent electric shock or equipment failure, 

  please do not turn on the power until completing wiring.

•  Never disassemble, modify, or repair the product. 

  There is a possibility of malfunction, electric shock, or a risk of fire.

• Please turn off the power when mounting / dismounting of the product. This is a cause of 

electric shock, malfunction, or failure.

Warning

Caution

Number

Name

Description

No. 1

Control input terminal (4 - 20 mA +)

Current input terminal from 

temperature controller, PLC, and etc

No. 2

Control input terminal (4 - 20 mA -)

No. 3

Circuit power supply (24 V d.c. +)

Power input for circuit drive with 

power supply(SMPS) and etc

No. 4

Circuit power supply (24 V d.c. -)

No. 5

Alarm1 (Middle alarm) +

Alarm terminal to PLC, relay, etc 

No. 6

Alarm1 (Middle alarm) -

No. 7

Alarm2 (Light alarm) +

Alarm terminal to PLC, relay, etc 

No. 8

Alarm2 (Light alarm) -

No. 9

R, S, T load power input

3 Phase AC load power input

No. 10
No. 11
No. 12

U, V, W load terminal

3 phase load connection

(Delta connection, Y connection, etc)

No. 13
No. 14

HEAD OFFICE/

FACTORY

HANYOUNGNUX CO.,LTD

28, Gilpa-ro 71beon-gil, Michuhol-gu, Incheon, Korea

TEL : +82-32-876-4697     FAX : +82-32-876-4696 

http://www.hanyoungnux.com

Reviews: