6
SUPPLEMENT TO HARDI
®
COMMANDER OPERATOR’S MANUAL
Operation
Adjustment of ECP operating controls
1. Power switch
2. Manual pressure regulation
3. Main ON/OFF
4. End nozzle (Left/OFF/Right)*
5. Foam marker regulation*
6. Foam marker (Left/OFF/Right)*
7. Boom section valves
8. Valve function A-B*
*optional equipment
Before spraying, adjust the ECP operating unit
using clean water (without chemicals).
1. Choose the correct nozzle (see manual). Make sure
that all nozzles are the same type and capacity.
2. Put the tractor in neutral and set the parking brake.
Adjust the P.T.O. r.p.m. to the number of revolutions
that will typically be used while spraying. This must
be kept between 300-600 r.p.m. (540 r.p.m. pump)
or 650-1100 (1000 r.p.m. pump) to ensure correct
operation of the HARDI-MATIC system.
3. Turn power switch
1
and main ON/OFF switch
3
to
the “ON” position.
4. Make sure all boom switches
7
are also in the “ON”
position. All nozzles should be spraying at this time.
5. Hold pressure regulating switch
2
up (+) or down (-)
until the approximate spraying pressure is shown on
the system pressure gauge.
Pressure
Control
Valve
Distribution
Valves
System Pressure
Gauge
Constant Pressure
Adjusting Screws
Adjustment of constant pressure
Note:
Disconnect power to the Spraybox to allow
for manual operation of the boom distribution
valves. Adjustment will be made one section at a
time until all valves have been adjusted.
6. Perform steps 1-5 and use the pressure reading from
step 5 throughout the constant pressure adjustment
procedure.
7. Manually shut-off the fi rst boom distribution valve by
turning the fi rst green handle (the fi rst boom section
should shut off).
8. Turn the adjusting screw under the valve just turned
off until the control pres sure gauge again shows
the same pressure as when all boom sections were
open (Turn the screw clockwise for higher pres sure,
counterclockwise for lower pressure).
9. Turn the boom distribution valve back on.
10. Repeat steps 6-9 for the remaining boom distribu-
tion valves.
Note:
Hereafter adjustment of the constant boom pres-
sure will only be needed if you change to nozzles with
other capacities, but not required if only changing pres-
sure or application rate using the same nozzles.
Operating the control unit while spraying
In order to shut off the entire boom, fl ip ON/OFF switch
3
to the "OFF" position. This returns all the pump
outputs to the main tank through the return system.
The diaphragm anti-drip valves ensure in stan ta neous
closing of all nozzles.
In order to shut off one or more sections of the boom,
switch the relevant distribution valve
7
to the "OFF"
position. The constant pressure system ensures that
the pres sure does not increase in the sections which
are still open.
In case of electrical failure, it is still possible to man u al ly
override all functions of the operating unit. To operate
manually, disconnect the multiplug from the Spraybox
fi rst and operate the handles by hand. It is possible to
change pressure and turn boom sec tions on or off.
Note:
Since the on-off switch normally op er ates by
shutting off all the boom distribution valves, you will
need to manually shut off all the distribution valves to
shut off the complete control unit manually.
IM POR TANT! When the sprayer is stored, the
Spraybox and the multiplug must be pro-
tected against moisture and dirt. A plastic
bag may be used to protect the multi plug. Store the
Spraybox in a clean dry place.
Summary of Contents for Commander Plus
Page 1: ...COMMANDER 67801103 8 10 Operator s Manual Supplement to ...
Page 2: ......
Page 4: ......
Page 11: ......