HARDY MANUFACTURING CO., INC (MODEL KB165) PAGE 8
2-4
Connection of Power to Heater
This unit must be wired by a qualified electrician
in accordance with the National Electrical Code.
Verify that all electrical power is turned off. Install a 20 amp circuit with #12/2 W/Gnd
NM Type UF wire from the power source through the 4” watertight pipe or other
means to the
heater
. This wire will connect to the “LINE” Terminals on the GFCI
Receptacle located on the rear of the Heater. The breaker installed at the power
source should be a 20 amp GFCI.
2-5
Wiring Diagram
This equipment must be installed in accordance
with the National Electrical Code.
( See wiring diagram next page )