10
HARGASSNER Heating technology for
Biomass
A 4952 Weng OÖ Tel.: +43/7723/5274-0 Fax: +43/7723/5274-5 office@hargassner.at
II
Safety regulations
3
Measures in case of danger
3.1
Fire in the boiler room
Switch-off main switch prior any fire-fighting operations
Disconnect main power supply
Switch-off the boiler and unplug the unit from the mains
3.2
After power loss
During the power failure, do not open the boiler's doors or reach into it.
Danger of deflagration
Danger of crushing through augers
After the electrical supply is switched on again, the control starts in
Heat up
mode
and monitors the flue gas temperature.
As the flue gas temperature increases, the boiler will heat up and control the
transfer of heat according to the preset parameters.
3.3
Leak in heating water system (no water)
If the water pressure is too low, not enough heat is being transferred from the
boiler to the heat circuits, HWT and accumulator.
Danger of boiler overheating
Turn off the boiler.
Fix leakiness
fill / refill water system
Check water pressure
3.4
Leak in the boiler (smoke escaping)
Turn off the boiler.
Check the seals of the doors and cleaning covers, and have them replaced.
3.5
Auger blockage(s)
Do not touch the augers.
Danger of crushing at sudden release of blockages
Briefly run the blocked augur backwards in manual
mode (two seconds
max.).
Danger of squeezing of fuel in the auger
Only clean the augers and remove blockages using suitable tools and when
the main power switch is turned off and locked
Summary of Contents for Classic 12
Page 64: ......