4
HARGASSNER Heating technology for
Biomass
A 4952 Weng OÖ Tel.: +43/7723/5274-0 Fax: +43/7723/5274-5 office@hargassner.at
I
Technical Data
Chapter I: Technical Data
1
Dimensions
2
Intended purpose
This automatic wood pellet boiler is designed to heat water only. Only fuels
permitted by Hargassner may be burned in this boiler. Only use the boiler if it is
in technically perfect condition. Rectify errors immediately.
The appropriate operation also covers observation of all items of this operation
manual and the carrying out of inspection- and maintenance works.
3
Fuel quality
Only use fuels that comply with
EN ISO 17225-2
(replaces
ÖNORM EN 14961-2
).
3.1
Wood Pellets (A1)
Ensure these quality standards are adhered to when wood pellets are ordered and
delivered.
• Least possible dust content
• Wood pellets with a hard and shiny surface
• 100% natural wood, no additives, etc.
• Wood pellet class
A1
defined in
EN ISO 17225-2:2014
and
ÖNORM M 7136
B
H
T
Designation
Description
Value
Unit
B
Total width
1165
mm
T
Total depth
775
mm
H
Total height
1470
mm
Total weight
300
kg
W A R N I N G
Only use released and permitted fuels
Always consult Hargassner before using new fuels.
Have their compatibility with the boiler checked by Hargassner.
Calorific
value
Density
Diameter
Length
Fine material
rate
> 4.6 kWh/kg
600 - 750 kg/m³
6
±
1 mm
3.15 - 40 mm
< 1%
Summary of Contents for Classic 12