10
P68 Pellet Stove
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to five feet high and at least three
inches from a combustible wall. This vertical sec-
tion will provide natural draft in the event of a power
failure.
If the stove is installed below grade be sure the
ve n t te
rmination is at least 18" above grade. The
outlet must also be 1 foot from the house/building.
Note: Do not place joints within wall pass-
throughs.
CAUTION
Keep combustible materials (such as grass,
leaves, etc.) at least 3 feet away from the flue
outlet on the outside of the building.
#1 Preferred method
This method provides excellent venting for nor-
mal operation and allows the stove to be installed
closest to the wall. Two inches from the wall is safe;
however, four inches allows better access to remove
the rear panel. The vertical portion of the vent should
be three to five feet high. This vertical section will
help provide natural draft in the event of a power fail-
ure.
Note: Do not place joints within wall pass-
throughs.
Venting
Fig. 8
3 ft.
to combustibles
Fig. 9
3 ft.
to combustibles
Combustibles
allowed
beyond 3 ft.
3 ft.
to combustibles
36" min
clearance to any
combus tible
material
12" min. wall to outlet
Combustibles
allowed
beyond 3 ft.
3 ft.
to combustibles
Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.