13
P68 Pellet Stove
#8 Installing through the ceiling
Thr ough the ce iling vent, follow PLvent
manufacturers recommendations when using wall
and ceiling pass through.
Note: Do not place joints
within wall pass-throughs.
Fig. 14
PL vent manufacturer's
fi re stop s pa ce r an d
support
(See Page 5 for
corner installation
clearances)
M inimum flue v ent
configuration
It is recommended that outside
air be installed with this venting
configuration to reduce smoke
and creosote smell in the room
in the event of power failure.
M
in
.
a
b
o
v
e
g
ro
u
n
d
le
v
e
l
1
8
"
Storm collar
Flashing
3" min.
3" min.
12" min.
3" min.
Venting
Fig. 15
3" min.
No ins ulation or
other combustible
ma te ri al s
ar e
allowed within 3" of
the PL vent pipe.
12" min. wall to outlet
36" m in clearance to any
com bustible m aterial
Fig. 16
Evaluation notes were added to the output document. To get rid of these notes, please order your copy of ePrint IV now.