background image

22

PC 45 Corn/Pellet Stove

 

 FEEDER DOES NOT FEED

1. No fuel in hopper.
2. Firebox draft may be too low for low draft pres-
sure switch in feeder circuit to operate. 

Check for

closed doors

, loose or missing gasket on doors

or hopper lid, faulty pressure switch.
3. Feed motor will not run until ESP senses 200

o

 F.

Maybe you  did not put  enough pellets in  the burn
pot before lighting the fire.
4.  Something  is  restricting  flow  in  the  hopper  or
causing the slide plate to stick.
5. Feed motor has failed.

PARTIALLY BURNED FUEL

1. Feed rate too high.
2. Draft too low.
3. Burn pot may need  to be cleaned.
4. Combination of all the above.
5.  #6  status  blink: A  6  blink  control  board  status
indication  is  caused  by  poor  or  incomplete  com-
bustion.  The  circuit  board has  the  ability  to  track
the combustion through feed settings and ESP tem-
peratures. When the control board has calculated
poor  or  incomplete  combustion  it  will  shut  down
the  unit as  a safety  feature.  (Poor or  incomplete
combustion is a contributer of creasote which may
cause a chimney fire)
A 6 blink status may be caused by several things:
1. Blocked or partially blocked flue.
2. Blocked or partially blocked inlet air.

a.  backdraft  damper  on  the  inlet  pipe  may  be

stuck  closed.

b. if outside air is installed the inlet cover may be

blocked.
3. The air chamber under the burnpot may be filled
with fines and small bits of ash.
4.  The  holes  in  the  burnpot  may  be  getting  filled
with ash or carbon buildup.
5.  Co mbus tio n  blower  f an  bla des   may  ne ed
cleaned.
6. There is no fuel in the hopper.

COMBUSTION BLOWER RUNS AFTER SHUT DOWN

This is a normal function. The combustion blower
will  run  for  5  hours  after  the  stove  is  completely
cool.

SMOKE  SMELL

Seal the vent  pipe joints and connection  to stove
with  silicone.

FIRE HAS GONE OUT

1. No fuel in hopper.
2. Draft setting is too low.
3. Something is restricting fuel flow.
4. Feed motor or draft motor has failed.
5. Power failure or blown fuse.

SMOKE  IS  VISIBLE COMING  OUT  OF  VENT

1. Air-fuel ratio is too rich.

A. Feed rate too high.
B. Draft too low caused by a gasket leak.

2. Unit is in an ignition cycle.

LOW HEAT OUTPUT

1. Feed rate too low
2. Temperature setting too low (Stove Temp Mode)
3. Draft too low because of gasket leak.
4. Poor quality or high moisture fuel.

PC 45  Trouble-Shooting

Cleaning Burn Pot

Whenever your stove is not burning, take the

opportunity to scrape the burn pot to remove car-
bon buildup. A vacuum cleaner is handy to remove
the residue. Be sure the stove is cold if you use a
vacuum.

Carbon buildup can be scraped loose with the

fire burning using the special tool provided with your
stove. Scrape the sides of the burnpot (corn grate),
and the floor  and sides (pellet grate).  The carbon
will be pushed out by the incoming fuel. Always wear
gloves to do this.

Removing Ashes

Turn the Temp Dial to number 1 approximately

30 minutes before removing ashes. This will result
in a cooler stove and ash pan.

Maximum  Feed  Adjuster  settings  are  not

needed  in  most  cases.  Operating  in  the  normal
range (#2 corn) (#4 pellet) is recommended when
maximum  heat  output  is  not  required.  The  ESP
probe prevents the stove from being over-fired.

Keep the stove free of dust and dirt.

Fuel

The PC 45 can burn corn with moisture levels

up to 16%, with 14.5% or less ideal.

Pellet fuels are put into 3 categories in terms of

ash  content.  Premium  at  1%  or  less,  Standard  at
3% or less  and all others at 3% or more.

The PC 45 is capable of burning all 3 catego-

ries of pellets due to a patented feeder and burn pot
system.

It should be noted, however, that higher ash con-

tent will require more frequent  ash removal and may
provide  less  BTU's  per  pound.  Normally,  standard
and high ash pellets cost less than premium pellets
and can be cost effective when burned in the PC 45.

The moisture content of pellets must not exceed

8%. Higher moisture will rob BTU's and may not burn
properly.

Helpful Hints

Summary of Contents for PC 45

Page 1: ...FETY FOLLOW INSTALLATIONDIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS INYOUR AREA CONTACT YOUR LOCAL AUTHORITY SUCH AS MUNICIPAL BUILD...

Page 2: ...2 PC 45 Corn Pellet Stove...

Page 3: ...Sidewinder Burn Pot allows corn to be burned from three days up to a week without cleaning depending on the corn s moisture level and burn rate Automatic Ignition allows you to fill the hopper set yo...

Page 4: ...cover panels are removed from the stove to make it easier to get at the hold down bolts The rear cover panels are packed inside the hopper and should be installed on the stove as shown It is recommend...

Page 5: ...o clock position Does the door rope compress If not loosen the set screw turn the paw bolt one more turn into the door Repeat as required to achieve a tight door fit NOTE Remember to thoroughly clean...

Page 6: ...me are closed If this readingis more than 05 higher thanthe unconnected reading check for possible restrictions or the need for outside air See page 8 Mobile Home Installation When installing this uni...

Page 7: ...hen measured fromthe horizontalcenter line of the regu lator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance to a non mechanical air sup ply inlet to t...

Page 8: ...ide surface temperature to allow a clearance to combustibles of only 3 inches The sections of pipe lock together to form an air tight seal in most cases however in some cases a per fect seal is not ac...

Page 9: ...tural draft in the event of a power failure 2 Preferred method This method also provides excellent venting for normaloperation but requires the stove tobe installed farther from the wall The vertical...

Page 10: ...you may want to install a liner as in method 6 4 Installing into an existing fireplace chimney US only This method provides excellent venting for nor mal operation This method also provides natural dr...

Page 11: ...sure to use approved pellet vent pipe fittings Seal pipe joints with silicone in addition to the sealing system used by the manufacturer Pipesize shouldbe increased to 4 using this method 6 Installing...

Page 12: ...19 Fig 20 7 Installing through the ceiling vent Through the ceiling vent follow PL vent manufacturers recommendations when using wall and ceiling pass through DO NOT INSTALL A FLUE DAMPER IN THE EXHAU...

Page 13: ...with a 3 setting being the maximum setting 1 the lowest setting This set ting will vary depending on the quality of corn used When burning pellets the feed rate setting can be adjusted within the ful...

Page 14: ...s you to check the motors for operation NOTE The auger motor will not operate with the view door or ash door open NOTE The initial start upona newstove may require the corn to be purged into the burnp...

Page 15: ...l board setting The unit can only go to low burn and will remain there until it runs out of fuel or until more heat is needed and the feed rate in creases Feed rate adjustments and dial settings are t...

Page 16: ...n the Temperature Dial to the desired setting 4 Clean the burnpot and housing if necessary 5 Fill the burnpot with pellets so that the auger tube opening is covered and slopes away from the auger tube...

Page 17: ...ithin off position band except after normal shut down Blinks to indicate errors listed below Indicates power to distribution blower 6 Blinks Indicates that the control has calculated poor or incomplet...

Page 18: ...bustion Motor Speed Control Low draft only set point The small straight screwdriver slot is plastic therefore the unit can be adjusted while in operation Fig 29 Fig 30 A simple draft test should be pe...

Page 19: ...e to carry and dispose of ashes 3 Slide the ash pan back into the stove Cleaning If you have been burning corn the stove will need to be cleaned approximately once a month The amount of corn burned an...

Page 20: ...ing nut on the feeder cover and slide the cover off the threaded rod 3 Remove all fines with a vacuum Fig 37 Brush not supplied Can be found in hardware stores Fig 33 Latch closed with blower coverin...

Page 21: ...against the burnpot grate and housing 9 Install the front plate lock 10 The dirty auger extension burnpot grate and front plate just removed can now be cleaned for the next scheduled maintenance NOTE...

Page 22: ...s restricting fuel flow 4 Feed motor or draft motor has failed 5 Power failure or blown fuse SMOKE IS VISIBLE COMING OUT OF VENT 1 Air fuel ratio is too rich A Feed rate too high B Draft too low cause...

Page 23: ...Mounting Bolts 3 30 1311812513 Air Pump 3 20 02679 Air Pump Mounting Hardware BHSCS 8 32 x 1 4 3 30 3108320252 3 8 MPT x 1 4 Barb Brass Inlet Fitting 3 10 724203 Pusher Arm Mtng Bolts 4 3 30 22520050...

Page 24: ...all the hold down clips and tighten with bolts as shown on page 5 To install ash lip trim simply slide the trim over the ash lip and into the groove on the trim Gold Door The gold door fig 43 is assem...

Page 25: ...or should be installed in the loca tion where you want to control the temperature NOTE Distances of more than 25 feet from the unit or in another room are not recommended The room sensor is essentialf...

Page 26: ...26 PC 45 Corn Pellet Stove PC 45 Wiring Diagram...

Page 27: ...9301 5 Single Fan Blade 3 20 40985 Combustion Blower 3 21 08639 Distribution Blower 3 21 22647 Hopper Lid Latch 3 31 199110 3 16 Rubber Washer for Hopper Lid 3 31 90131101 Power Cord 3 20 29685 Fire B...

Page 28: ...Damage and or repairs including but not limited to remote controls filters fuses knobs glass ceramic brick panels ceramic fiber afterburners door packing tile ceramic log sets paint batteries or batt...

Reviews: