9
PC 45 Corn/Pellet Stove
Fig. 12
3 ft.
to
combustibles
3 ft.
to
combustibles
Venting
#1 Preferred method
This method provides excellent venting for nor-
mal operation and allows the stove to be installed
closest to the wall. Two inches from the wall is safe;
however, four inches allows better access to remove
the rear panel. The vertical portion of the vent should
be three to five feet high. This vertical section will
provide natural draft in the event of a power failure.
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to five feet high and at least three
inches from a combustible wall. This vertical sec-
tion will provide natural draft in the event of a power
failure.
If the stove is installed below grade the vent
termination should be at least 1 foot above grade.
CAUTION
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the flue outlet on the
outside of the building.
Fig. 13