background image

Harman®  •  Absolute43 Installation Manual_R2  •  2015 - ___ •  03/15

19

3-90-00778i

E. Locating Your Appliance & Chimney

Location of the appliance and chimney will affect performance. 
•  Install through the warm airspace enclosed by the building 

envelope. This helps to produce more draft, especially 

during lighting and die-down of the fire.

•  Penetrate the highest part of the roof. This minimizes the 

effects of wind loading.

•  Locate  termination  cap  away  from  trees,  adjacent 

structures, uneven roof lines and other obstructions.

•  Minimize the use of chimney offsets. 
•  Consider the appliance location relative to floor and ceiling 

and attic joists.

G. Negative Pressure

F. Draft

Draft is the pressure difference needed to vent appliances 

successfully. When an appliance is drafting successfully, all 

combustion  byproducts  are  exiting  the  home  through  the 

chimney.
Considerations for successful draft include:
•  Negative pressure in the firebox
•  Location of appliance and chimney
To measure the draft or negative pressure on your appliance 

use  a  magnahelic  or  a  digital  pressure  gauge  capable  of 

reading 0 - 1 inches of water column (W.C.).

 

The  appliance  should  be  running  on  high  for  at  least  15 

minutes for the test.
With the stove running on high you should have a negative 

pressure equal to or greater than the number given in the 

chart below. If you have a lower reading than you find on the 

chart, your appliance does not have adequate draft to burn 

the fuel properly.

Minimum Vacuum Requirements:

.20 - .25

Prior to installing the flue pipe, connect a draft meter. (The 

draft meter must have a minimum range of 0 - .5”) Record the 

first reading. Connect flue pipe to stove and be sure all doors 

and windows in the home are closed. Record the second draft 

reading _______. If the second reading is more than .05” 

lower than the first reading, check for possible restrictions 

or the need for outside air. For more information on the draft 

test procedure, 

refer to “Appliance Set-Up” Section C.

•  DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE 

SERVICING ANOTHER APPLIANCE.

•  DO  NOT  CONNECT  TO ANY AIR  DISTRIBUTION 

DUCT OR SYSTEM.

May allow flue gases to enter the house

CAUTION

!

Negative pressure results from the imbalance of air available 

for the appliance to operate properly. It can be strongest in 

lower levels of the house.
Causes include:
•  Exhaust fans (kitchen, bath, etc.)
•  Range hoods
•  Combustion air requirements for furnaces, water heaters 

and other combustion appliances

•  Clothes dryers
•  Location of return-air vents to furnace or air conditioning
•  Imbalances of the HVAC air handling system
•  Upper level air leaks such as: 
  -  Recessed lighting
  -  Attic hatch
  -  Duct leaks
To minimize the effects of negative air pressure:
•  Install the outside air kit with the intake facing prevailing 

winds during the heating season

•  Ensure adequate outdoor air for all combustion appliances 

and exhaust equipment

•  Ensure furnace and air conditioning return vents are not 

located in the immediate vicinity of the appliance

•  Avoid installing the appliance near doors, walkways or 

small isolated spaces

•  Recessed lighting should be a “sealed can” design
•  Attic hatches weather stripped or sealed
•  Attic mounted duct work and air handler joints and seams 

taped or sealed

Risk of Asphyxiation!

  Negative  pressure  can  cause 

spillage of combustion fumes and soot.

WARNING

!

NOTICE

HEARTH & Home Technologies assumes no responsibility 

for  the  improper  performance  of  the  chimney  system 

caused by:
•  Inadequate draft due to environmental conditions
•  Downdrafts
•  Tight sealing construction of the structure
•  Mechanical exhausting devices

Summary of Contents for Absolute43

Page 1: ...ng codes prior to installation Installation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspec...

Page 2: ...n 9 4 Termination Location and Vent Information A Vent Termination Minimum Clearances 10 14 B Chimney Diagram 15 C Venting Use of Elbows 16 17 D Outside Air 18 E Locating Your Appliance and Chimney 19...

Page 3: ...wall roof flashing installed and sealed ________________________________ Terminations installed and sealed ________________________________ Electrical Section 1 Pg 4 120VAC unswitched power provided t...

Page 4: ...ault efficiency and the burn rates from the low and high EPA tests Based on the maximum feed rate per hour multiplied by approximately 8600 BTU s which is the average BTU s from a pound of pellets E E...

Page 5: ...Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation o...

Page 6: ...any component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance can...

Page 7: ...anual_R2 2015 ___ 03 15 7 3 90 00778i 24 9 16 24 1 16 15 6 1 8 7 15 16 29 1 2 27 7 16 1 1 1 4 3 Clearances Figure 3 1 A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for r...

Page 8: ...safety but do not leave much room for access when cleaning or servicing Please take this into account when placing the stove Alternate floor protector dimension may be used as long as they satisfy th...

Page 9: ...low the smaller U S floor protection requirements ONLY if the user agrees to completely shut down the appliance and allow it to cool to where all fire is extinguished and the combustion blower and its...

Page 10: ...also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least 1 from...

Page 11: ...xisting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is que...

Page 12: ...t vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into a...

Page 13: ...gure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level Minimum flue vent configuration It is rec...

Page 14: ...ay to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the t...

Page 15: ...vertical clearance to a ventilated soffit located above the terminal within ahorizontal distance of2feet 60 cm fromthe center line of the terminal must be a minimum of 18 E The clearance to an unventi...

Page 16: ...ble horizontal venting length is 4 ft for 3 4 pellet vent pipe Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical p...

Page 17: ...ude 10 Ft 15 Ft 20 Ft 25 Ft 30 Ft 5 Ft 0 Ft 15 Ft Equivalent Vent Length EVL Maximum Horizontal Run Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more fr...

Page 18: ...tion must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilation to the space in...

Page 19: ...s in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air For more...

Page 20: ...a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with at least three screws and sealed with high temp silicone caulking 4 stainless ste...

Page 21: ...intain regularly Conveniently locate a ClassAfire extinguisher to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department J Inspect Appliance Compo...

Page 22: ...l line voltage Note During this test the combustion fan will not achieve its top RPM of 3200 due to the density of the ambient air All RPM displays could vary 50 from that of the set RPM s Allow sever...

Page 23: ...m as the stove Clothing and other flammable materials should not be placed on or near this stove Installation and repair of this stove should be done by a qualified service person The appliance should...

Page 24: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 24 3 90 00778i B Wiring Diagram...

Page 25: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 25 3 90 00778i...

Page 26: ...in U S A Copyright 2015 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns Fo...

Reviews: