background image

Harman®  •  Absolute43 Installation Manual_R2  •  2015 - ___ •  03/15

20

3-90-00778i

H. Avoiding Smoke and Odors

Negative Pressure, Shut-down, and Power Failure:
To reduce the probability of back-drafting or burn-back in 

the pellet burning appliance during power failure or shut-

down conditions, the stove must be able to draft naturally

 

without exhaust blower operation. Negative pressure in the 

house will resist this natural draft if not accounted for in the 

pellet appliance installation.
Heat rises in the house and leaks out at upper levels. This 

air must be replaced with cold air from outdoors, which flows 

into  lower  levels  of  the  house.  Vents  and  chimneys  into 

basements and lower levels of the house can become the 

conduit for air supply, and reverse under these conditions.

Outside Air

An outside air kit is recommended in all installations. The 

Outside Air Kit must be ordered separately.
Per national building codes, consideration must be given to 

combustion air supply to all combustion appliances. Failure 

to supply adequate combustion air for all appliance demands 

may lead to back drafting of those and other appliances. 
When the appliance is roof vented (strongly recommended): 

The air intake is best located on the exterior wall oriented 

towards the prevailing wind direction during the heating 

season.

When the appliance is side-wall vented: 

The air intake is best located on the same exterior wall 

as the exhaust vent outlet and located lower on the wall 

than the exhaust vent outlet.

The outside air supply kit can supply most of the demands 

of the pellet appliance, but consideration must be given to 

the total house demand. 
House  demand  may  consume  the  air  needed  for  the 

appliance. It may be necessary to add additional ventilation 

to the space in which the pellet appliance is located. 
Consult with your local HVAC professional to determine the 

ventilation demands for your house.

Vent Pipe

Be sure to use approved pellet vent pipe wall and ceiling 

pass- through fittings to go through combustible walls and 

ceilings. Be sure to use a starting collar to attach the venting 

system to the stove. The starting collar must be secured to 

the flue stub with at least three screws, and sealed with high 

temp silicone caulking. 
4”  stainless  steel  flex  vent  piping  is  only  allowed  for  use 

in masonry fireplaces and chimneys or factory built wood-

burning fireplaces with class A metal chimneys.

Pellet venting pipe is constructed of two layers with air space 

between the layers. This air space acts as an insulator and 

reduces the outside surface temperature to allow a clearance 

to  combustibles  of  only  1  inch. The  sections  of  pipe  lock 

together to form an air tight seal in most cases; however, in 

some cases a perfect seal is not achieved. For this reason 

and  the  fact  that  the Absolute43  operates  with  a  positive 

vent pressure, we specify that the joints also be sealed with 

silicone or aluminum tape in addition to the sealing system 

used by the manufacturer.
Where passing through an exterior wall or roof, use silicone 

to maintain an effective vapor barrier at the location where 

the chimney or component penetrates to the exterior of the 

structure.

Vent Configurations:

To  reduce  probability  of  reverse  drafting  during  shut-

down  conditions,  Hearth  &  Home  Technologies  strongly 

recommends:
•  Installing the pellet vent with a minimum vertical run of 

five feet, preferably terminating above the roof line.

•  Installing the outside air intake at least four feet below the 

vent termination.

To prevent soot damage to exterior walls of the house and 

to prevent re-entry of soot or ash into the house:
•  Maintain specified clearances to windows, doors, and air 

inlets, including air conditioners.

•  Vents should not be placed below ventilated soffits. Run 

the vent above the roof.

•  Avoid venting into alcove locations.
•  Vents should not terminate under overhangs, decks or 

onto covered porches.

•  Maintain  minimum  clearance  of  12  inches  from  the 

vent termination to the exterior wall. If you see deposits 

developing  on  the  wall,  you  may  need  to  extend  this 

distance to accommodate your installation conditions.

Hearth & Home Technologies assumes no responsibility 

for, nor does the warranty extend to, smoke damage 

caused by reverse drafting of pellet appliances under 

shut-down or power failure conditions.

Summary of Contents for Absolute43

Page 1: ...ng codes prior to installation Installation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspec...

Page 2: ...n 9 4 Termination Location and Vent Information A Vent Termination Minimum Clearances 10 14 B Chimney Diagram 15 C Venting Use of Elbows 16 17 D Outside Air 18 E Locating Your Appliance and Chimney 19...

Page 3: ...wall roof flashing installed and sealed ________________________________ Terminations installed and sealed ________________________________ Electrical Section 1 Pg 4 120VAC unswitched power provided t...

Page 4: ...ault efficiency and the burn rates from the low and high EPA tests Based on the maximum feed rate per hour multiplied by approximately 8600 BTU s which is the average BTU s from a pound of pellets E E...

Page 5: ...Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation o...

Page 6: ...any component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance can...

Page 7: ...anual_R2 2015 ___ 03 15 7 3 90 00778i 24 9 16 24 1 16 15 6 1 8 7 15 16 29 1 2 27 7 16 1 1 1 4 3 Clearances Figure 3 1 A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for r...

Page 8: ...safety but do not leave much room for access when cleaning or servicing Please take this into account when placing the stove Alternate floor protector dimension may be used as long as they satisfy th...

Page 9: ...low the smaller U S floor protection requirements ONLY if the user agrees to completely shut down the appliance and allow it to cool to where all fire is extinguished and the combustion blower and its...

Page 10: ...also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least 1 from...

Page 11: ...xisting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is que...

Page 12: ...t vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into a...

Page 13: ...gure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level Minimum flue vent configuration It is rec...

Page 14: ...ay to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the t...

Page 15: ...vertical clearance to a ventilated soffit located above the terminal within ahorizontal distance of2feet 60 cm fromthe center line of the terminal must be a minimum of 18 E The clearance to an unventi...

Page 16: ...ble horizontal venting length is 4 ft for 3 4 pellet vent pipe Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical p...

Page 17: ...ude 10 Ft 15 Ft 20 Ft 25 Ft 30 Ft 5 Ft 0 Ft 15 Ft Equivalent Vent Length EVL Maximum Horizontal Run Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more fr...

Page 18: ...tion must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilation to the space in...

Page 19: ...s in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air For more...

Page 20: ...a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with at least three screws and sealed with high temp silicone caulking 4 stainless ste...

Page 21: ...intain regularly Conveniently locate a ClassAfire extinguisher to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department J Inspect Appliance Compo...

Page 22: ...l line voltage Note During this test the combustion fan will not achieve its top RPM of 3200 due to the density of the ambient air All RPM displays could vary 50 from that of the set RPM s Allow sever...

Page 23: ...m as the stove Clothing and other flammable materials should not be placed on or near this stove Installation and repair of this stove should be done by a qualified service person The appliance should...

Page 24: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 24 3 90 00778i B Wiring Diagram...

Page 25: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 25 3 90 00778i...

Page 26: ...in U S A Copyright 2015 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns Fo...

Reviews: