background image

Harman®  •  Absolute43 Installation Manual_R2  •  2015 - ___ •  03/15

9

3-90-00778i

NOTE:

 Measurement "L" is even with the 

rear of the hopper in the US ONLY

NOTE:

 Measurement “K” is measured from 

the glass in the US ONLY

L

J

Floor Protection 

Requirements

US

Canada

Sides

Rear

6" 

200mm

1" 

25mm

K

Front

6" 

450mm

E.  Floor Protection

Place the stove on a noncombustible floor or floor protector 

that extends a minimum of 6 inches (152mm) to the front 

of the load door opening, 6 inches (152mm) to the sides of 

the door opening, and 1 inches to the rear. Floor protection 

must also extend 2 inches (51mm) beyond each side of any 

horizontal flue pipe. The minimum floor protector material 

is 20 gauge sheet metal. Other floor protector materials are 

ceramic tile, stone, brick, etc. Figure 3.3

NOTE for Canadian installation only:

 Per ULC-S627-00, 

if  installed  on  a  combustible  floor,  the  need  to  provide  a 

noncombustible 

floor protector 

covering the area beneath 

the 

space heater 

and extending at least 17.72” (450mm) on 

the firing side and at least 7.87” (200mm) on the other sides.

In  Canada,  you  may  follow  the  smaller  U.S.  floor 

protection requirements ONLY if the user agrees to 

completely shut-down the appliance, and allow it to cool 

to  where  all  fire  is  extinguished  and  the  combustion 

blower and its indicator light shuts off, prior to opening 

the firebox door or ash door.

Minimum Size floor protection (USA) is 25-7/8” wide By 28” 

deep (658mm X 711mm).
*Floor  protection  dimensions  for  the  front  and  sides  are 

measured from the appliance door opening in The United 

States. In Canada, the side dimension is measured from the 

widest part of the appliance.

F. Mobile Home Installation

When  installing  this  unit  in  a  mobile  home,  several 

requirements must be followed: 
1.  The unit must be bolted to the floor in places. This can 

be done using 1/4” lag screws through the skid bolt down 

holes located at the base of the unit. 

Note:

 Lag bolt must 

be installed from the bottom up. 

2.  The  unit  must  be  connected  to  an  outside  combustion 

air  inlet.  Proper  supports  and  spark  arresters  must  be 

considered  when  installing  venting.  See  “Termination 

Location and Vent Information” Section D.

3.  Floor  protection  and  clearances  must  be  followed  as 

shown.

4.  Unit must be grounded to the metal frame of the mobile 

home.

Figure 3.3

J

USA

K

L

J

CANADA

F

loor

 

protector

L

Install 1/4” lag bolts here.

Summary of Contents for Absolute43

Page 1: ...ng codes prior to installation Installation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspec...

Page 2: ...n 9 4 Termination Location and Vent Information A Vent Termination Minimum Clearances 10 14 B Chimney Diagram 15 C Venting Use of Elbows 16 17 D Outside Air 18 E Locating Your Appliance and Chimney 19...

Page 3: ...wall roof flashing installed and sealed ________________________________ Terminations installed and sealed ________________________________ Electrical Section 1 Pg 4 120VAC unswitched power provided t...

Page 4: ...ault efficiency and the burn rates from the low and high EPA tests Based on the maximum feed rate per hour multiplied by approximately 8600 BTU s which is the average BTU s from a pound of pellets E E...

Page 5: ...Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation o...

Page 6: ...any component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance can...

Page 7: ...anual_R2 2015 ___ 03 15 7 3 90 00778i 24 9 16 24 1 16 15 6 1 8 7 15 16 29 1 2 27 7 16 1 1 1 4 3 Clearances Figure 3 1 A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for r...

Page 8: ...safety but do not leave much room for access when cleaning or servicing Please take this into account when placing the stove Alternate floor protector dimension may be used as long as they satisfy th...

Page 9: ...low the smaller U S floor protection requirements ONLY if the user agrees to completely shut down the appliance and allow it to cool to where all fire is extinguished and the combustion blower and its...

Page 10: ...also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least 1 from...

Page 11: ...xisting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is que...

Page 12: ...t vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into a...

Page 13: ...gure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level Minimum flue vent configuration It is rec...

Page 14: ...ay to the top of the chimney The chimney should be inspected and cleaned before installing your stove If you discover that the chimney does not have a clay tile liner or has cracks or flaking of the t...

Page 15: ...vertical clearance to a ventilated soffit located above the terminal within ahorizontal distance of2feet 60 cm fromthe center line of the terminal must be a minimum of 18 E The clearance to an unventi...

Page 16: ...ble horizontal venting length is 4 ft for 3 4 pellet vent pipe Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical p...

Page 17: ...ude 10 Ft 15 Ft 20 Ft 25 Ft 30 Ft 5 Ft 0 Ft 15 Ft Equivalent Vent Length EVL Maximum Horizontal Run Long runs of flex or PL vent pipe installed directly vertical from the flue stub may require more fr...

Page 18: ...tion must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilation to the space in...

Page 19: ...s in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air For more...

Page 20: ...a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with at least three screws and sealed with high temp silicone caulking 4 stainless ste...

Page 21: ...intain regularly Conveniently locate a ClassAfire extinguisher to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department J Inspect Appliance Compo...

Page 22: ...l line voltage Note During this test the combustion fan will not achieve its top RPM of 3200 due to the density of the ambient air All RPM displays could vary 50 from that of the set RPM s Allow sever...

Page 23: ...m as the stove Clothing and other flammable materials should not be placed on or near this stove Installation and repair of this stove should be done by a qualified service person The appliance should...

Page 24: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 24 3 90 00778i B Wiring Diagram...

Page 25: ...Harman Absolute43 Installation Manual_R2 2015 ___ 03 15 25 3 90 00778i...

Page 26: ...in U S A Copyright 2015 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns Fo...

Reviews: