background image

11

These  units  are  pre-tested  at  the  factory  with 

exactly 120 Volts A.C., 60 Hz. They are checked 

and adjusted  for firebox tightness, gasket leakage, 

motor operation and igniter operation.  The Advance 

is then factory set at a mid-point adjustment and in 

most cases will not need any adjustments.  

NOTE: 

The factory low draft setting may not be correct 

for the unit's permanent installation conditions.

The control board on the Advance is equipped with 

a low draft adjustment port, located on the control 

face just to the right of the igniter light. See Figure 

14. This voltage adjustment is provided to allow the 

unit to be adjusted for the household voltage where 

the  unit  is  going  to  be  in  permanent  operation. 

NOTE: The line voltage varies from area to area 

and often home to home.

The  low  draft  voltage  should  be  adjusted  to 

achieve  the  most  efficient  burn  on  low  burn  or 

"maintenance".  This  voltage  adjustment  allows 

the installer to change the low voltage set point 

approximately 15 volts.  This adjustment should be 

done by the installer during set up because a draft 

meter reading is 

required 

to insure proper set up.

If the unit is not  adjusted properly, it does not 

cause a safety concern. If the unit is adjusted too 

high, only efficiency is lost. If the unit is adjusted 

too low, the low draft pressure switch will not allow 

the feeder motor or the igniter to operate. 

A  simple  draft  test  should  be  performed  after 

completing the flue pipe installation. To record the 

results for future reference:

1.  Plug unit into a 120 VAC, 60 HZ outlet.

2.  Close the hopper lid, front view door, and the 

ash pan. Neither pellets nor a fire are required for 

this test.

3.  With the mode selector in the "OFF" position, 

turn the feed adjuster to "TEST".

4.  Record the high draft_____in W.C. (Normal is 

-.50 to -.60) The control will be on the High draft 

for a total of 2 minutes.

5.  After 1 minute, the combustion motor will go 

down to low draft and the distribution blower will go 

on high. Allow approximately 15 seconds to pass 

for the combustion motor to slow before checking 

the low draft.

6.  If the low draft is between .35 and .45, record 

the reading _____ in W.C.  If the reading is higher, 

slowly turn the set screw counter-clockwise until the 

draft lowers. If the reading is lower, very slowly turn 

the set screw clockwise until the draft increases.

 

NOTE: In some cases, the draft may not go as 

low as .35 even with the set screw completely 

counter-clockwise.

Combustion Motor 

Speed Control

Low draft only set 

point.

The  small  straight 

screwdriver  slot  is 

plastic;  therefore,  

the  unit  can  be 

adjusted  while  in 

operation.

Fig.14

draft Meter bolt hole location

Fig.15

:

low draft voltage Adjustment

Summary of Contents for Advance Pellet Stove

Page 1: ...YOUR SAFETY FOLLOW INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA Contact your local authority such as munic...

Page 2: ......

Page 3: ...Do not install appliance in a sleeping room An outside combustion air inlet must be provided The structural integrity of the manufactured home floor ceiling and walls must be maintained Refer to manu...

Page 4: ...generally on 4 can be increased if higher burn rates are necessary The unit s maximum burn rate should not create less than 1 of ash on the burn pot front edge See Fig 2 Page 5 Overfeeding is not a sa...

Page 5: ...he unit to burn for about 30 minutes and check ash on front of burn pot Fig 2 If the ash line is larger than 1 turn the feed adjuster from 4 to 5 Allow another 30 minutes of burn time and check again...

Page 6: ...Manual position after the ignition cycle begins The difference between AUTO Room Temperature Mode and Manual Room Temperature Mode is that the fire will not go out as the room temperature goes above...

Page 7: ...pot Fig 5 If the ash line is larger than 1 turn the feed adjuster from 4 to 5 Allow another 30 minutes of burn time and check again If at 6 setting a 1 or less ash bed is not obtainable it is not a pr...

Page 8: ...for more details A six blink status may be set if the stove is allowed to run out of pellets To reset turn mode selector to OFF then back on to the desired mode If the unit was not out of pellets see...

Page 9: ...en cleaning or servicing Please take this into account when placing the stove Installation When installing this stove in a mobile home several requirements must be followed 1 The unit must be bolted t...

Page 10: ...shield Using a 5 16 nut driver or socket loosen the 2 screws about 4 or 5 turns Figure 12 Slide the rear shields straight outward until the ends come out of the rear retaining clips as seen in Fig 13...

Page 11: ...y efficiency is lost If the unit is adjusted too low the low draft pressure switch will not allow the feeder motor or the igniter to operate A simple draft test should be performed after completing th...

Page 12: ...than 25 feet from the unit or in another room are not recommended It is recommended that the room sensor be installed even if only installed on the rear of the unit as a return air sensor The room sen...

Page 13: ...ide air connection will supply the demands of the pellet appliance but consideration must be given to the total house demand House demand may consume some air needed for the stove especially during a...

Page 14: ...rear panel which must be removed before connecting the flex pipe The pipe should be run outside and terminate to the side or below the vent pipe outlet so the flue outlet is more than 12 from the inle...

Page 15: ...tion and allows the stove to be installed closest to the wall One inch from the wall is safe however two or three inches allows better access to remove the rear panel The vertical portion of the vent...

Page 16: ...aowool mineral wool or an equivalent non combustible insulation is recommended to be installed on top of the sealing plate to reduce the possibility of condensation Acap should be installed on the chi...

Page 17: ...ould be increased to 4 using this method This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure In Canada and some places i...

Page 18: ...min 3 min 3 min Fig 26 3 min It is recommended that outside air be installed with this venting configuration CAUTION Keep any materials that may be affected by the elevated exhaust temperatures at le...

Page 19: ...m above a gas meter regulator assembly when measured from the horizontal center line of the regulator 1 I The clearance to service regulator vent outlet must be a minimum of 6 feet 1 J The clearance t...

Page 20: ...A ROOM DESIGNATED FOR SLEEPING WARNING Keep combustibles away from flue outlet CAUTION CAUTION THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR WALL AND CEILING ROOF MUST BE MAINTAINED Keep combustib...

Page 21: ...ig 32 Fig 33 Maintenance Emptying Ashes Formation and Need For Removal The products of combustion will contain small particles of fly ash The fly ash will collect in the exhaust venting system and res...

Page 22: ...skets for worn or missing pieces Replace if necessary Fig 37 Closing When closing the door always hold the door latch all the way up until it has caught the receiving bolt Then push the latch downward...

Page 23: ...leads the wires inside the burn pot and the cold leads the wires from the control board are always pulled to the rear of the feeder body Not coiled inside the burn pot It is very important that these...

Page 24: ...el into the left corner of the firebox with the panel resting on the top edges of the burn pot Rotate the right side of the brick panel through the door opening Reverse this operation to reinstall the...

Page 25: ...l the combustion intake cover by first sliding the right side tab into the retainer slot seen in Figure 47 Rotate the cover inward until the cover fits into its hole Make sure the two faces Fig 46 of...

Page 26: ...t and left baffle are interchangeable 6 Now remove the heat exchanger baffle plates See Fig 50 51 To remove the left plate slide the center lock to the right To remove the right plate slide the center...

Page 27: ...d igniter circuits This is to protect against reaching into the feed mechanism while in operation The Control Board ESP combination is responsible for all high limit safety control There are 2 high li...

Page 28: ...rol board status indication is caused by poor or incomplete combustion The circuit board has the ability to track the combustion through feed settings and ESP temperatures When the control board has c...

Page 29: ...takes energy to dry and tends to cool the appliance thus robbing heat from your home Damp pellet fuel could turn back into sawdust which does not flow properly through the feed system Size Pellets are...

Page 30: ...e 2 3 8 inches Fuse Rating 6 amp BTU Range 0 to 48 000 Feed Rate 1 0 lbs hr on minimum 6 lbs hr on maximum Flue Size 3 inch Pellet Vent Pipe Maximum Wattage 480 Watts Start cycle and test Start Cycle...

Page 31: ...U B B E R C O R D GREEN WIRE IS GROUND BONDED TO STOVE BODY P O W E R C O R D CONTACTS LOW PRESSURE SWITCH N O LT BLUE GREEN WHITE RED WHITE BLACK MALE FEMALE CONNECTIONS LT BLUE BROWN WHITE WHITE PLU...

Page 32: ...truction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlie...

Page 33: ...ult of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enam...

Page 34: ...435 1 10 09876A Y gasket Hopper Top 1 00 375501 Y Switch Hopper 48 Post 008362469 3 20 232108 Y Additional service parts on following page Advance Pellet Stove 1 70 08730 2 Charcoal Ending Manufacturi...

Page 35: ...inge Pkg of 20 1 00 129004 Y 4 Hopper Heat Shield Rev A 2 00 06612B 5 Top 4 00 08739P 6 Tile Set Cream 3 43 03000 1 No longer available 3 43 03000 2 Black 3 43 03000 3 No longer available 3 43 03000 4...

Page 36: ...11 Y gasket glass 15 Ft 1 00 2312 Y glass Large Front 3 40 08728 Y glass Side 3 40 08729 Y glass Clips 1 Set 1 00 06600 15 Retainer Assembly for Combustion Blower cover 1 10 08553S Y 16 Combustion Int...

Page 37: ...ts Spacers 25 Sets 1 00 960026 24 8 Sprocket Replacement Kit 1 00 06626 Y 24 9 3 4 Feeder Tensioner 3 31 00075 Y 24 10 3 1 2 Sprocket 2 00 06626M Y 24 11 Chain 60 Pin 3 50 06667 Y 24 12 3 1 2 Sprocket...

Page 38: ...t Ultra Air Intake Pkg of 10 3 44 677160 10 Y 25 7 Ultra Feeder Weldment 1 10 724132 Y 25 8 UL Feeder Pusher Arm 1 10 677131W Y 25 9 Fines deflector No longer available 2 00 677138 10 25 10 gasket UL...

Page 39: ...50 Y 26 4 Bushing 3 8 Od x 1 4 OAL Pkg of 5 3 50 00058 5 Y 26 5 Latch Bushing 3 8 Od x 5 16 OAL Pkg of 5 3 50 08288 5 Y 26 6 Nut 1 4 20 Zinc Plated Finished Hex Pkg of 100 3 30 8004 100 Y 27 1 Firebox...

Page 40: ...Set temperature knob to desired amount Turn mode selector knob onto Room Temp mode After the fire has lit watch that the fuel does not feed too fast that it pushes the red glowing fuel bed off of the...

Page 41: ...operation Your appliance will recognize when power is restored What happens depends on ESP temperature and whether it is equipped with automatic ignition In Automatic setting units equipped with auto...

Page 42: ...Service Maintenance Log 42 Date Of Service Performed By Description Of Service...

Page 43: ......

Page 44: ...e This powerful heating appliance boasts uncompromising attention to detail and helps preserve our planet by using environmentally responsible fuels Signature of Boxer Your premium quality hearth prod...

Reviews: