background image

Harman®  •  Allure50 Installation Manual_R2  •  2016 - ___ •  09/16

21

3-90-888000i

Appliance Set-Up 

 

A. Unpacking

The Allure50 is bolted (1/4 x 1" hex head bolts) to the skid to 

prevent movement during shipping. 
To free the stove from the skid you must remove the hold-

down bolts from both the left and right hand side shipping 

brackets using a 7/16” socket or wrench. Figure 5.1.

B. Firebox Draft and Combustion Fan RPM

These units are pre-tested at the factory with exactly 120 VAC, 

60 Hz. They are checked and adjusted for firebox tightness, 

gasket leakage, motor operation and igniter operation. The 

Allure50 is then factory set at a mid-point adjustment and in 

most cases will not need any adjustments.
Check and record the firebox draft before installing venting 

and after venting is installed 

(before starting fire)

.

There is a draft meter port located in the back of the unit at 

the pressure switch where draft can be measured. Install the 

magnahelic meter 

(capable of at least .5” of water column) 

Figure 5.2.
Connect  the  power  cord  to  a  120  VAC,  60Hz  grounded 

receptacle. (A surge protector is recommended to protect 

the circuit board.) Also be sure that the polarity of the outlet 

that the stove is plugged into is correct.
Go to the “Home Screen”, the power icon should be gray. 

Press menu, on the first menu page press “test” icon.
The test page has 4 component test modes. The second icon 

is for the combustion fan test.
One press of the icon turns the combustion fan to full line 

voltage. 

(Note: During this test , the combustion fan will 

not achieve its top RPM of 3200 due to the density of the 

ambient air.)

 All RPM displays could vary +/- 50 from that 

of the set RPM’s. Allow several minutes for the fan motor to 

warm up.
Press the icon a second time, the combustion fan will go 

to “Maximum” (as set in the 

Authorized Dealer Only

 area 

under the combustion fan icon)

The “Maximum” is factory set at 2900 RPM. Allow the RPM 

to stabilize and record the firebox draft Maximum.
 

Before Install: __________ IWC

 

After Install: __________ IWC

(Firebox Draft and Combustion Fan RPM Cont.)

Press the icon a third time, the combustion fan will go to 

“Minimum”  (as  set  in  the 

Authorized Dealer Only

 area 

under the combustion fan icon) allow the RPM to stabilize 

and record the firebox draft minimum.
 

Before Install: __________ IWC

 

After Install: __________ IWC

Cold Stove Draft:

2500 RPM 

Low -.20 and -.25

2900 RPM 

High -.45 and -.50

Leaving  the  test  page  will  end  any  tests  in  progress  and 

goes back to whatever mode of operation it was set to on 

the home page.
If the unit is not adjusted properly, it does not cause a safety 

concern. If the unit is adjusted too high, only efficiency is lost. 

If the unit is adjusted too low, the low draft pressure switch 

will not allow the feed motor or the igniter to operate.

Figure 5.1

Shipping Bolts (4)

(2) Bolts are located on the front 

and rear of the unit.

Figure 5.2

MAGNEHELIC

INCHES OF WATER

0

.10

.20

.30

.40

.50

The rear panel will need to be removed prior to installing the draft 
meter  to  the  barbed  tee.  Be  sure  to  hold  the  barbed  tee  while 
removing the plug cover. Replace plug cover after draft test.

Summary of Contents for Allure50

Page 1: ... fire Check building codes prior to installation Installation MUST comply with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspection requirements in your area To obtain a French translation of this manual please contact your dealer or visit www harmanstoves com Pour obtenir une traduction française de ce manu...

Page 2: ...cation and Vent Information A Vent Termination Minimum Clearances 10 13 B Chimney Diagram 14 C Venting Use of Elbows 15 16 D Outside Air 17 E Locating Your Appliance and Chimney 18 F Draft 18 G Negative Pressure 18 H Avoiding Smoke Odors 19 I Fire Safety 20 J Inspect Appliance Components 20 5 Appliance Setup A Unpacking 21 B Firebox Draft and Combustion Fan RPM 21 6 Reference Materials A Safety Re...

Page 3: ...wall roof flashing installed and sealed ________________________________ Terminations installed and sealed ________________________________ Electrical Section 1 Pg 4 120VAC unswitched power provided to the appliance ________________________________ Appliance Setup Section 5 Pg 21 22 All packaging and protective materials are removed ________________________________ Accessories installed properly _...

Page 4: ...herwise operate this wood heater in a manner inconsistent with operating instructions in this manual This wood heater needs periodic inspection and repair for proper operation It is against federal regulations to operate this wood heater in a manner inconsistent with operating instructions in this manual E Electrical Codes 115 VAC 60 Hz Start 3 5 Amps Run 2 5 Amps D BTU Efficiency Specifications 1...

Page 5: ...ulations Consult insurance carrier local building inspector fire officials or authorities having jurisdiction over restrictions installation inspection and permits It is a good idea to plan your installation on paper using exact measurements for clearances and floor protection before actually beginning the installation Consideration must be given to Safety convenience traffic flow Placement of the...

Page 6: ...component not approved by Hearth Home Technologies Install parts or components not Listed or approved Disable safety switches Improper installation adjustment alteration service or maintenance can cause injury or property damage For assistance or additional information consult a qualified installer service agency or your dealer Hearth Home Technologies disclaims any responsibility for and the warr...

Page 7: ...ation Manual_R2 2016 ___ 09 16 7 3 90 888000i 3 Clearances Figure 3 1 A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference only 39 7 8 38 3 4 21 1 4 1 3 8 26 5 8 13 3 4 6 1 38 3 4 8 9 16 ...

Page 8: ...s shown in Figure 3 2 Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing Please take this into account when placing the stove When installing the unit into an alcove it is important to consider the required clearances listed below 42 High 33 1 4 Wide Height 51 Width 36 1 4 Depth 24 B Non Combustible Materials Specification Materia...

Page 9: ...llowed 1 The unit must be bolted to the floor This can be done using an appropriate fastener for the application 2 The unit must be connected to an outside combustion air inlet Proper supports and spark arresters must be considered when installing venting See Termination Location and Vent Information Section D 3 Floor protection and clearances must be followed as shown 4 Unit must be grounded to t...

Page 10: ...nt venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of the vent should be three to five feet high and at least 1 from a combustible wall This vertical section will provide natural draft in the event of a power failure Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer If the stove ...

Page 11: ...place chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questionable you may want to install a liner as in method 5 In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney The chimney should be inspected and clea...

Page 12: ...et vent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into an existing chimney Figure 4 6 w Full liner This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure In some places in the US...

Page 13: ...LT CAUTION 12 min wall to outlet 36 min clearance to any combustible material Figure 4 7 Figure 4 8 Figure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as shrubbery mulch or tall grasses 12 min above ground level Minimum flue vent configuration It is recommended that outside air be installed with this venting configuration Smoke spillage may be possi...

Page 14: ...porch deck or balcony is fully open on a minimum of 2 sides beneath the floor See NFPA 211 for more installation clearance reductions when using outside air Where passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 if in Canada WARNING Venting terminals must not be recessed into a wall or siding Only PL vent pipe wall pass throu...

Page 15: ...e Example First Floor Installation A unit is to be installed using 3 Pellet Pipe with 3 feet of horizontal pipe a Tee 10 feet of vertical pipe a 90 elbow and a termination cap The equivalent vent length is 3 ft of Horizontal Pipe 1 x 3 EVL 3 EVL 90 Elbow or Tee 1 x EVL 5 EVL 10 ft of Vertical Pipe 10 x 5 EVL 5 EVL 90 Elbow or Tee 1 x EVL 5 EVL Termination Cap 0 EVL Equivalent Vent Length 18 EVL In...

Page 16: ...e combustion blower outlet 4 stainless steel flex vent piping is only allowed for use in masonry fireplaces and chimneys or factory built wood burning fireplaces with Class A metal chimneys All pellet vent pipe must be secured together either by means provided by pipe manufacturer or by 3 screws at each joint Use only the specified venting components Use of any other components will void the produ...

Page 17: ...e total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilation to the space in which the pellet appliance is located Consult with your local HVAC professional to determine the ventilation demands for your house To install outside air use 3 non combustible flex pipe There is a break away hole on the rea...

Page 18: ... in the home are closed Record the second draft reading _______ If the second reading is more than 05 lower than the first reading check for possible restrictions or the need for outside air For more information on the draft test procedure refer to Appliance Set Up Section C DO NOT CONNECT THIS UNIT TOACHIMNEY FLUE SERVICING ANOTHER APPLIANCE DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM M...

Page 19: ...rough combustible walls and ceilings Be sure to use a starting collar to attach the venting system to the stove The starting collar must be secured to the flue stub with at least three screws and sealed with high temp silicone caulking 4 stainless steel flex vent piping is only allowed for use in masonry fireplaces and chimneys or factory built wood burning fireplaces with Class A metal chimneys P...

Page 20: ...aintain regularly Conveniently locate a ClassAfire extinguisher to contend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department J Inspect Appliance Components Remove appliance and components from packaging and inspect for damage Report to your dealer any parts damaged in shipment Read all the instructions before starting the installation Follow these...

Page 21: ...ion fan to full line voltage Note During this test the combustion fan will not achieve its top RPM of 3200 due to the density of the ambient air All RPM displays could vary 50 from that of the set RPM s Allow several minutes for the fan motor to warm up Press the icon a second time the combustion fan will go to Maximum as set in the Authorized Dealer Only area under the combustion fan icon The Max...

Page 22: ... as the stove Clothing and other flammable materials should not be placed on or near this stove Installation and repair of this stove should be done by a qualified service person The appliance should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required It is imperative that control compartments burners and circulating air passageways of...

Page 23: ...E CAPACITOR SKY BLUE BLACK SKY BLUE YELLOW PRESSURE SWITCH GREEN YELLOW ANY IEC POWER CORD RATED FOR 120 VAC 10 AMP 250 VAC 10 AMP SKY BLUE YELLOW SKY BLUE BROWN GREEN YELLOW LINE FILTER INSIDE BURNPOT IGNITER ELEMENT COMBUSTION MOTOR SENSOR ALLURE ABSOLUTE 63 DISTRIBUTION BLOWERS CABLE GOING TO TOUCH CONTROL GROUND TO STOVE BODY BACKUP ESP G R E E N Y E L L O W GROUND TO FEEDER BODY DARK BLUE SKY...

Page 24: ... in U S A Copyright 2015 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For the location of your nearest Harman dealer please visit www harmanstoves com ...

Reviews: