Connecting the Optional Thermostat
if the optional thermostat is used, it must be plugged
into the terminal strip located in the left rear corner of the
heater.
When installing a millivolt control system, use only
a special low resistance thermostat. Do not use a regular
heating thermostat.
Be sure that all electrical connections are clean, free
from corrosion, and tight. inspect connections periodically
to confirm that no corrosion has built up over time.
When properly installed and maintained, a millivolt
control system should give many years of trouble-free
service.
it is important to use wire of a gauge proper for the
length of the wire:
RECOMMENDED WIRE GAUGES
Maximum
Wire
Length
Gauge
100'
14
60'
16
40'
18
25'
20
15'
22
Connecting the Cordset
the clarity Direct vent Gas heater must be installed
in accordance with local codes or, in the absence of local
codes, with the most recent edition of the national electri-
cal code ansi/nFPa 70, or the current canadian electrical
code c22.1.
note: the convection fan requires a 120 vac supply
for operation, but the heater can be operated without the fan
as in the case of a power outage.
Plug the 3-prong grounded electrical cord plug into
the wall.
WARNING: This heater is equipped with a three-
pronged grounding plug that should be plugged
directly into a properly grounded receptacle. Do not
cut or remove the grounding prong from the plug.
CONNECTING THE HEATER TO CORDSET
rear view of clarity
terminal strip
location