30
3-90-233R24_11/13
8.
Turn the mIN. TEmP. dial
on the control board to the
desired Minimum temperature. This will start the lighting
process if the temperature at the aquastat sensor is
approximately 5° F. less than the set temperature on the
MAX TEMP. dial.
9.
Fill hopper
with pellets and
remove ashes
as required.
Type of Fuel
- Use pelletized wood only. The lower the
ash content of the pellets the less cleaning that will be
needed of the heat exchanger tubes. The cleaner these
tubes are kept, the more efficient the boiler will be.
NOTE: Do not burn garbage, gasoline, naphtha, engine
oil, or other inappropriate materials in this appliance.
Store pellets in the manufacturer’s wrapping until needed
to prevent pellets from absorbing moisture. do not store
fuel within the appliance installation clearances, or within
the space required for fueling, ash removal, and other
routine maintenance operations.
Operation
lighting A Fire manually
Lighting the fire manually will not be necessary unless the
ignition system fails.
Follow steps 1 through 5 of the instructions for automatic
lighting.
6.
Flip the Igniter Switch down
into the “MANUAL-LIGHT”
position. See Fig. 12.
7. Open the firebox door to access the burnpot.
8. Fill the burnpot with pellets as shown.
See Fig. 14.
Only fill level with the front edge.
( ------- dO NOT OvErFIll ------- )
9. Have matches or other ignition source ready.
10. Turn mode Selector
to desired MIN TEMP setting.
This will start the combustion blower and allow the ESP to
control the fire in relation to the MAX TEMP Dial setting.
(The MAX TEMP dial setting must always be set above the
MIN TEMP setting) Once the fire is well established the MAX
TEMP dial can remain on any temperature setting desired.
durINg mANuAl OPErATION:
SPECIAl NOTE: when the Switch is set to manual ignite
position, the boiler will function as in auto mode, except
the fire will not be allowed to go out. It will only be allowed
to go to a minimum burn rate between the times the
aquastat is calling for heat. This rate is about
1.1 pound
of fuel per hour. If used in manual mode, be sure there
is an overheat dump in place. Note that if the overheat
dump zone does not provide sufficient cooling, and the
water temperature reaches 220 deg, the feed motor will
be forced to shut off. because the unit is set on manual
Ignition, it will not re-ignite when the water temperature
cools below the settings.
Fig. 12
Fig. 13
Never attempt to start a fire if there is no power or if
the combustion blower is not operating.
Never open the hopper lid during a fire if there is no
power or if the combustion blower is not operating.
Fig. 14