background image

Harman®  •  P43 Installation Manual_R23  •  2008 -___  •  04/14

18

3-90-04301i

H. Avoiding Smoke and Odors

Negative Pressure, Shut-down, and Power Failure:

T

o reduce the probability of back-drafting or burn-back in 

the pellet burning appliance during power failure or shut-

down conditions, the stove must be able to draft naturally

 

without exhaust blower operation. Negative pressure in the 

house will resist this natural draft if not accounted for in the 

pellet appliance installation.
Heat rises in the house and leaks out at upper levels. This 

air must be replaced with cold air from outdoors, which flows 

into  lower  levels  of  the  house.  Vents  and  chimneys  into 

basements and lower levels of the house can become the 

conduit for air supply, and reverse under these conditions.

Outside Air

An outside air kit is recommended in all installations.  The 

Outside Air Kit must be ordered separately.
Per national building codes, consideration must be given to 

combustion air supply to all combustion appliances.  Failure 

to supply adequate combustion air for all appliance demands 

may lead to back drafting of those and other appliances.  
When the appliance is roof vented (strongly recommended):  

The air intake is best located on the exterior wall oriented 

towards the prevailing wind direction during the heating 

season.

When the appliance is side-wall vented: 

The air intake is best located on the same exterior wall 

as the exhaust vent outlet and located lower on the wall 

than the exhaust vent outlet.

The outside air supply kit can supply most of the demands 

of the pellet appliance, but consideration must be given to 

the total house demand.  
House  demand  may  consume  the  air  needed  for  the 

appliance.  It may be necessary to add additional ventilation 

to the space in which the pellet appliance is located.  
Consult with your local HVAC professional to determine the 

ventilation demands for your house.

Vent Configurations:

To  reduce  probability  of  reverse  drafting  during  shut-

down  conditions,  Hearth  &  Home  Technologies  strongly 

recommends:
•  Installing the pellet vent with a minimum vertical run of 

five feet, preferably terminating above the roof line.

•  Installing the outside air intake at least four feet below the 

vent termination.

To prevent soot damage to exterior walls of the house and 

to prevent re-entry of soot or ash into the house:
•  Maintain specified clearances to windows, doors, and air 

inlets, including air conditioners.

•  Vents should not be placed below ventilated soffits. Run 

the vent above the roof.

•  Avoid venting into alcove locations.
•  Vents should not terminate under overhangs, decks or 

onto covered porches.

•  Maintain  minimum  clearance  of  12  inches  from  the 

vent termination to the exterior wall. If you see deposits 

developing  on  the  wall,  you  may  need  to  extend  this 

distance to accommodate your installation conditions.

Hearth & Home Technologies assumes no responsibility 

for, nor does the warranty extend to, smoke damage 

caused by reverse drafting of pellet appliances under 

shut-down or power failure conditions.

Vent Pipe

Be sure to use approved pellet vent pipe wall and ceiling pass- through fittings to go through combustible walls and ceilings. 

Be sure to use a starting collar to attach the venting system to the stove. The starting collar must be secured to the flue stub 

with at least three screws, and sealed with high temp silicone caulking. 
4" stainless steel flex vent piping is only allowed for use in masonry fireplaces and chimneys or factory built woodburning 

fireplaces with class A metal chimneys.
Pellet venting pipe (also known as Type L vent) is constructed of two layers with air space between the layers. This air space 

acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of only 1 inch. The 

sections of pipe lock together to form an air tight seal in most cases; however, in some cases a perfect seal is not achieved. 

For this reason and the fact that the P43 operates with a positive vent pressure, we specify that the joints also be sealed 

with silicone.
Where passing through an exterior wall or roof, be sure to use the appropriate pass-through device providing an adequate 

vapor barrier. Venting manufacturers generally provide these pass-through devices. 

Summary of Contents for P43

Page 1: ...with local regional state and national codes and regulations Contact local building or fire officials about restrictions and installation inspection requirements in your area Tested and approved for...

Page 2: ...tions 4 E Non Combustible Materials Specification 4 F Combustible Materials Specification 4 G Electrical Codes 4 2 Getting Started A Design and Installation Considerations 5 B Tools and Supplies Neede...

Page 3: ...l roof flashing installed and sealed ________________________________ Terminations installed and sealed ________________________________ Electrical Section 1 Pg 4 120VAC unswitched power provided to t...

Page 4: ...will be voided by the below actions DO NOT Install or operate damaged appliance Modify appliance Install other than as instructed by Hearth Home Technologies Operate the appliance without fully assemb...

Page 5: ...vent termination CAUTION If burning shelled field corn you must use approved venting specifically designed for corn to prevent corrosion or degradation Follow the instructions from the venting manufa...

Page 6: ...installation Follow these instructions carefully during the installation to ensure maximum safety and benefit WARNING Risk of Fire or Explosion Damaged parts could impair safe operation DO NOT instal...

Page 7: ...n Manual_R23 2008 ___ 04 14 7 3 90 04301i 20 3 4 22 10 33 1 2 5 1 8 13 3 4 28 5 16 3 Clearances Figure 3 1 A Appliance Dimension Diagram Dimensions are actual appliance dimensions Use for reference on...

Page 8: ...to consider the required clearances to walls see Figure 3 2 Figure 3 2 10 254mm with side shields 16 406mm without side shields 2 51mm 36 914mm 10 254mm 16 406mm 9 228mm With or Without Side Shields...

Page 9: ...e pipe The minimum floor protector material is 20 gauge sheet metal Other floor protector materials are ceramic tile stone brick etc Figure 3 3 NOTE for Canadian installation only Per ULC S627 00 If i...

Page 10: ...wall pass through 2 Preferred method Figure 4 2 This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall The vertical portion of t...

Page 11: ...ting fireplace chimney Figure 4 4 This method provides excellent venting for normal operation This method also provides natural draft in the event of a power failure If the chimney condition is questi...

Page 12: ...ent pipe fittings Seal pipe joints with silicone or aluminum tape in addition to the sealing system used by the manufacturer Pipe size should be increased to 4 using this method 6 Installing into an e...

Page 13: ...ed by the manufacturer Note Do not place joints within wall pass through Figure 4 7 Figure 4 8 Figure 4 9 Area within dotted circle represents the minimum clearance to combustible materials such as sh...

Page 14: ...is fully open on a minimum of 2 sides beneath the floor NOTE Where passage through a wall or partition of combustible construction is desired the installation shall conform to CAN CSA B365 if in Canad...

Page 15: ...ical from the flue stub may require more frequent cleaning due to fly ash falling off inside and collecting directly above the combustion blower outlet Any use of horizontal venting will require more...

Page 16: ...liance but consideration must be given to the total house demand House demand may consume some air needed for the stove especially during a power failure It may be necessary to add additional ventilat...

Page 17: ...he flue pipe connect a draft meter The draft meter must have a minimum range of 0 5 Record the first reading Connect flue pipe to stove and be sure all doors and windows in the home are closed Record...

Page 18: ...mends Installing the pellet vent with a minimum vertical run of five feet preferably terminating above the roof line Installing the outside air intake at least four feet below the vent termination To...

Page 19: ...tend with small fires In the event of a hopper fire Evacuate the house immediately Notify fire department J Inspect Appliance Components Remove appliance and components from packaging and inspect for...

Page 20: ...l sides of the burn pot and that the back of the guide rests against the body of the stove Figure 5 3 INSTALL EXHAUST VENT AT CLEARANCES SPECIFIED BY THE MANUFACTURER Most pellet vent pipe requires a...

Page 21: ...nt should be done by the installer during set up because a draft meter reading is required to insure proper set up Combustion Motor Speed Control Low draft only set point The small straight screwdrive...

Page 22: ...stove and could result in a House fire Use only approved fuels and operation guidelines The stove is hot while in operation Keep children clothing and furniture away Contact may cause skin burns CAUT...

Page 23: ...ONTACTS N O MALE FEMALE CONNECTIONS BONDED TO STOVE BODY GREEN WIRE IS GROUND P O W E R C O R D 1 8 3 R U B B E R C O R D WHITE GREEN BLUE GREEN WHITE RED MALE FEMALE CONNECTIONS BROWN WHITE MALE FEMA...

Page 24: ...U S A Copyright 2012 Harman a brand of Hearth Home Technologies Inc 352 Mountain House Road Halifax PA 17032 www harmanstoves com Please contact your Harman dealer with any questions or concerns For t...

Reviews: