14
P68 Pellet Stove
#8 installing through the ceiling
Through the ceiling vent, follow PL vent
manufacturers recommendations when using wall
and ceiling pass throughs.
note: do not place joints
within wall pass-throughs.
Minimum flue vent
configuration
It is recommended that
outside air be installed with
this venting configuration to
reduce smoke and creosote
smell in the room in the event
of power failure.
Min. above ground level
18"
venting
Fig. 15
Fig. 14
PL vent manufacturer's
firestop spacer and
support
(See Page 7 for
corner installation
clearances)
Storm collar
Flashing
3" min.
3" min.
12" min.
3" min.
3" min.
No insulation or
other combustible
materials are
allowed within 3" of
the pellet vent pipe.
Unless specified
by the pipe
manufacturer
12" min. wall to outlet
36" min clearance to any
combustible material
Fig. 16
Shaded area represents
the minimum clearance to
combustible materials such as
shrubbery, mulch or tall grasses.