13
P61A Pellet Stove
3-90-05822R29_JR15_04/14
12"
min. abo
ve g
round lev
el
#7 installing through the ceiling
Through the ceiling vent, follow PL vent manufacturers
recommendations when using wall and ceiling pass through.
note: do not place joints within wall pass-throughs.
Figure 14
venting
Figure 15
Figure 16
PL vent manufacturer's
firestop spacer and support
1" MIN.
No insulation or other
combustible materials
are allowed within 3"
of the PL vent pipe.
flashing
storm collar
1" MIN.
1" MIN.
12" MIN
1” MIN.
Minimum flue vent configuration
It is recommended that outside air be
installed with this venting configuration.