HS-3100/3200 Programming Manual
24
The Dialer Settings window has the following push buttons along the right side:
•
Exit:
Close the Dialer Settings window and return to the IDs window.
•
Configuration 1:
Display the Dialer Configuration 1 dialog.
•
Configuration 2:
Display the Dialer Configuration 2 dialog.
•
Call Directions:
Display the Call Directions dialog.
•
Zone Data:
Display the Zone Data dialog.
•
Maintenance/Common:
Display the Dialer Maintenance and Common Reporting Codes
dialog.
Dialer Configuration 1
The
Dialer Configuration 1
dialog (see
Figure 11
)
contains the First
Communicator Options,
Second Communicator
Options and International
Options.
The
Communications
option
determines if the dialer will
communicate to the central
station. When Enabled is
selected, the dialer will
communicate all events as
programmed. When
Disabled is selected, the
dialer will not communicate any events.
The
TLM One/Two Check
options determine whether the dialer will test for telephone line faults on
line one and line two respectively.
The
Third Phone #
can be programmed for two different modes of operation. When Alternate
Dialing Enabled is selected, the dialer switches between the first and third telephone numbers
after each dialing attempt, until the maximum number of dialing attempts have been made to each
number. When Third Number Backup is enabled, the dialer will use the third telephone number
only if all attempts to communicate to the first telephone number fail. If all attempts to
communicate to the third number also fail, a failure to communicate trouble will be generated.
When Disabled is selected, the third telephone number is not used.
The
Dialing
option has three different options for pulse or DTMF dialing. If All attempts Pulse is
selected, the dialer will always use pulse (rotary) dialing. If All attempts DTMF Dialing is selected,
the dialer will always use DTMF dialing. If 4 attempts DTMF then Pulse is selected, the dialer will
use DTMF dialing for the first four attempts. If unsuccessful, the dialer will switch to pulse (rotary)
dialing for the remaining attempts.
The
SIA Rep. Codes
option determines whether the dialer will send the automatic reporting codes
that are in the dialer, or use the reporting codes that are programmed in the
Zone Data
and
Maintenance/Common
reporting codes sections. See See “7.0 Appendix D: Table of Reporting
Codes” on page 56 for a list of the automatic SIA Reporting Codes.
The
SIA Max Events
option sets the maximum number of events the dialer will send for one SIA
transmission. When 20 per Round is selected, SIA sends a maximum of 20 events per round.
When 8 per Round is selected, SIA sends maximum of 8 events per round.
The
Contact ID Rep. Codes
option determines whether the dialer will send the automatic reporting
codes that are in the dialer, or use the reporting codes that are programmed in the Zone Data and
Figure 11: Dialer Configuration 1