HS-3100/3200 Programming Manual
25
Maintenance/Common reporting codes sections. See See “7.0 Appendix D: Table of Reporting
Codes” on page 56 for a list of the automatic Contact ID Reporting Codes.
The
Test Transmission Line
option determines how the dialer chooses a telephone line to send the
automatic test transmission. If Alternate is selected, the dialer will alternate between using
Telephone Lines 1 and 2 for transmissions, regardless of telephone line troubles. If Available is
selected, the dialer will use Telephone Line 1 for transmissions. If a trouble exists on Telephone
Line 1, the dialer will switch to Line 2.
When the
Force Dialing
option is set to enabled, if the first attempt by the panel to call the
monitoring station fails, on every subsequent attempt the panel will dial regardless of the presence
of dial tone. When Disabled is selected, the panel will not dial the programmed telephone number
if dial tone is not present.
When the
Busy Tone Detection
option is enabled, if busy tone is detected, the dialer will disengage
the phone line and try to place the call again following the delay between dialing attempts. When
Disabled is selected, the dialer will use the standard dialing procedure for every attempt.
The
Pulse Make/Break Ratio
option is for panels in international applications. When 40/60 is
selected, the pulse dialing make/break ratio is the 40/60. When 33/67 is selected, the pulse dialing
make/break ratio is 33/67.
The
Handshake
option determines the handshake used for BPS transmissions. When 1600 Hz is
selected, the dialer responds to a 1600 Hz handshake. When Standard is selected, the dialer
responds to the handshake designated by the format selected (1400 or 2300 Hz).
The
ID Tone
can be set to 1300Hz or 2100 Hz. The panel will emit a tone at the selected frequency
for 500 ms every 2 seconds when it places a call to indicate that it is a digital equipment call, not
voice. When Disabled is selected, this feature will not be used.
Dialer Configuration 2
The Dialer Configuration
2 screen (see
Figure 12
)
contains the Swinger
Shutdown Variables, Test
Transmission options and
Other Options.
The
Swinger Shutdown
options determine the
maximum number of
zone events and trouble
events that the dialer will
transmit in one day. The
trouble or alarm will still
be displayed on the panel
and logged in the archive,
but the dialer will not
transmit the event. There
are individual counters for
Zone Alarm and Restore, Zone Supervisory and Restore, Zone Trouble and Restore and
Maintenance Trouble and Restore. This feature will be reset at midnight. To disable the feature,
program 000.
The
Test Transmission Time of Day
determines when the automatic test transmission will occur.
The entry is four digits (HH:MM). To disable the feature, program the time as [9999].