Internal Circuit 99, Common Trouble:
This circuit is tripped by any internal circuit or
trouble condition not associated with an internal circuit that turns on the Common Trouble
LED on the panel. This circuit is used to annunciate common trouble conditions at a
remote location. This circuit is not tripped by troubles generated by input circuits or
addressable devices. This circuit is not recorded in the archive of the panel.
Figure 19: Internal Circuits Window
Internal Circuits List
The
Internal Circuits List
displays all of the internal circuits for the current Control Panel. Each line
includes the internal circuit number, its description and if relates have been assigned.
Warning:
Some of the internal circuits (e.g. checksum) do not have restore signals associated
with them. They generally relate to a condition that requires either service work or a reboot of the
panel. Any relates assigned to such an internal circuit have no way to be reset short of re-booting
the entire network.
Pushbuttons
The following push buttons are available:
•
List Entries:
This new feature allows the user to control the information displayed.
Relevant only
lists items applicable to the current version only.
All
lists all possible items
so that relates made on previous versions may be removed.
•
Exit:
Closes the Internal Circuits Window and returns to the Panel Window.
•
Reset:
Clears all relates associated with the current internal circuit.
•
Relate:
Opens the Relate Window for the internal circuit. This allows for the programming
of outputs, LEDs, relays and control modules to be operated by the internal circuit.
•
Copy Relates:
Copies the relates from another input to the current internal circuit (see
Figure 21). The values of the panel and circuit are required. Press Copy to copy the
information. If the function type of the two circuits is different, a requester is presented to
confirm the copy.
•
Map:
Displays and/or updates the Map Window. See section 2.8 Map Window of the
Network Plus User Guide
.
•
Verify List:
Displays the Verify List. If there is no Verify List, a requester will appear asking
whether you wish to perform a verification. See section 2.6.5 of the
Network Plus User
Guide
for a full description of the Verify List and its uses.