HS-3100/3200 Programming Manual
38
Switches Menu
This function can be set to Privilege Level 1 or 2. View or change the status of any switches.
These switches can be set to On, Off or Auto. The Auto state only applies to switches that have a
timer associated with them. The Auto state allows the switch to follow the timer settings. Any
changes made are broadcast to the network so that all panels have the same state. Settings are
retained by the panel if it is re-booted and the Master Unit broadcasts its settings to the network
upon start up. See
Switches Window
for information on programming what the switch affects.
The menu has the following options:
•
Individual:
View or change the status of an individual switch. Each switch is shown in
turn. If a switch has no timer, the Auto option is not shown.
•
All Off:
Force switches into the Off mode. The number displayed is the number of timers
that are switched On. This option is shown only if no switches have timers associated with
them.
•
All Auto:
Force all switches with timers to Auto mode. All switches with timers go into the
state dictated by the time. The number displayed is the number of switches with timers
forced On or Off. This option has no effect on switches without timers. This option is not
shown if no timers are associated with the switches.
Battery
Displays the current battery status. The display shows:
Line 1: Screen Title
Line 2: AC State (diagnostic use only)
Line 3: Current State of the Battery and Menu Option (see below)
Line 4: Menu Options (listed below)
The menu has the following options:
•
OK:
Return to Program Menu.
•
Test:
Force an immediate battery test.
•
Calibrate:
This function is restricted to Privilege Level 2. This calibrates the Battery
Charger. The batteries must be disconnected before beginning calibration. No keypad
control is provided during calibration. The calibration display will return when calibration is
over. Calibration only needs to be done when the configuration is erased. All Battery
Chargers come calibrated from the factory.
Addressable
The menu has the following options:
•
Reset Max/Min:
Clears the stored values for the maximum and minimum values returned
by the addressable devices. These values are automatically cleared when the panel
reboots.
•
Duplicates Check:
This causes an immediate check to see if more than one device is
using an address. The panel automatically does this check on the hour.
•
LED Mode:
This controls how the LEDs on the devices are used. There are three options:
-- OFF/FLASH:
The device LEDs are normally off and flash when an alarm is reported.
The flashing LED is reset when
System Reset
is pressed.
--
FLASH/ON:
The device LEDs flash each time they are polled. They latch on in Alarm.
The LEDs are reset when
System Reset
is pressed.
Note:
Due to current draw
limitations, only the first 5 detectors on a circuit latch their LEDs. This has no effect on
other panel operation.
--
OFF/ON:
The LEDs are normally off and latch on in Alarm. The LEDs are reset when
System Reset
is pressed.
Note:
Due to current draw limitations, only the first 5
detectors on a circuit latch their LEDs. This has no effect on other panel operation.
--
RESET:
This functions resets the LEDs to their off state.
Summary of Contents for HS-3100