HS-3100/3200 Programming Manual
50
5*
Bells
Displays the current status of the bell circuits. Also shows the
timers and settings for the cut-off. See screen 11 for acceptable
supervision values.
6
Function Relays
Displays the current settings and timers for the 4 function relays.
7
Releasers
Displays the current settings and timers for the releasing circuits
(if any).
8
Common Relays
Displays the current status of the 3 common system relays. Also
shows which relays may be disconnected by the
Common
Disconnect
hot-key.
9*
Alarm List
Shows the current alarm list. This is the same list that is
displayed on the LCD menu. Each screen in the LCD
corresponds to one line on the terminal screen. See Appendix A
for a description of the condition codes and zone numbers.
Commands
J
Page down
0 J
Go to the end of the list
K
Page up
0 K
Go to the beginning of the list
10*
Miscellaneous
Troubles
Display a list of all the troubles currently displayed by the
STATUS/MISC. TROUBLES selection from the LCD.
11*
Output
Supervision
Shows the current supervision readings and status for the bells
and auxiliary power circuits. These values should be in the range
130 to 150 for Vhi, and 10 to 20 for Vlo (low gain) or around 100
for Vlo (high gain). If the numbers are jumping all over the place,
there is a hardware fault with the terminal board.a
12
Relay Summary
Displays the relays and functions that have been activated:
Commands
O
Bell Circuits 1 to 8
F
Function Relays 1 to 4
A
Common Alarm
S
Common Supervisory
T
Common Trouble
G
Grount Fault
W
Walk Test
L
LCD Back Light
13*
Archive
Displays the Archive History List. This is the list of the last 900
(approximate) events that happened. See Appendix A for a
description of the condition codes and zone numbers.
Commands
J
Page down
0 J Go to the end of the list
K
Page up
0 K Go to the beginning of the list
Screen
Name
Description