The menu includes access to the STANDBY, INFORMATION,
ERRORS, PROGRAM PARAMETERS, CONFIGURATION,
CASCADE, and SERVICE menus. The UP and DOWN buttons
are used to position the arrow next to the desired option and the
ENTER button is pushed to access that option.
3.11.1.2 Configuring the Control
First push the MENU button and then select PROGRAM PARAMETERS from the menu. A screen opens that
allows the user to view and change various operating parameters.
Select the CH SETTINGS to adjust parameters related to the
boilers Comfort Heat function.
For example, selecting the SETPOINT parameter opens up a
screen that allows the setpoint to be changed.
The UP or DOWN buttons are used to adjust the CH setpoint up
or down as desired.
3.11.1.3 Other Control Parameters
Other parameters are available and may be changed by contacting the factory for assistance. The ENVI
®
Control
Getting Started Guide contains additional information regarding the operation of this control.
NOTICE!
Changing parameters requires an understanding of the parameters and the functionality of the boiler.
The boiler may not function properly if parameters are changed from the factory values.
3.12 C
OMBUSTION
A
DJUSTMENT
There is no required start-up or field adjustments for air flow control. The air flow is set at the factory.
3.12.1 Fuel/Air Ratio Adjustment
The fuel/air ratio is controlled by the automatic air gas ratio valve. This valve is adjusted at the factory to give 5.8-
6.5 % O2 at high fire and 7.0-7.5% O2 at low fire in the exhaust gas. However, the fuel/air ratio should be
Menu
Standby
Information
Errors
Menu
Standby
Information
Errors
Parameters
CH settings
DHW settings
Boiler settings
Parameters
CH settings
DHW settings
Boiler settings
CH settings
Setpoint 180
°F
BLR OP 1
CH mode 0
CH settings
Setpoint 180
°F
BLR OP 1
CH mode 0
CH settings
Setpoint 180
°F
BLR OP 1
CH mode 0
CH settings
Setpoint
Value: 180°F
Range: 45°F – 185°F
CH settings
Setpoint
Value: 180°F
Range: 45°F – 185°F
Summary of Contents for 1004905923
Page 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Page 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Page 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Page 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Page 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...