A##
A Code Error
Int. nr
Description
A01
IGNIT ERROR
1
Three unsuccessful ignition attempts in a row
A02
TOO MANY FLAME FAILURES
24
Three times flame was lost during on demand
A03
T MAX LOCK ERROR
18
Overheat stat is open
A05
GV RELAY ERROR
5
Problems with gas valve relay= internal hardware error
(pump not running)
A06
SAFTEY RELAY ERROR
6
Problems with gas valve relay = internal hardware error
(pump not running)
A09
RAM ERROR
9
Internal software error
A09
FLAG BYTE INTEGRITY ERROR
27
Internal software error
A09
AD HI CPL ERROR
28
Internal software error
A09
AD LO CPL ERROR
29
Internal software error
A09
REGISTER ERROR
33
Internal software error
A10
E2PROM ERROR
12
No communication with E2prom
A12
WRONG EEPROM SIGNATURE
10
Contents of Eprom is not up-to-date
A13
STATE ERROR
13
Internal software error
A14
ROM ERROR
14
Internal software error
A15
15MS XRL ERROR
16
Internal software error
A16
20 MS XLR ERROR
22
Internal software error
A18
STACK ERROR
19
Internal software error
A19
FLAME OUT TOO LATE ERROR
20
Flame still present 10 sec. after closing the gas valve
A20
FLAME ERROR I
21
Flame detected just before gas valve opened
A30
HIGH GAS PRESSURE ERROR
32
Gas pressure is to high
A31
LOW GAS PRESSURE ERROR
31
Gas pressure is to low
A32
41MS ERROR
23
Internal software issue
A33
FAN ERROR
8
Fan deviation more than300 rpm longer than 1 minute
(when fan speed > 4200 rpm this error is ignored)
A34
AIR PRESS SW NOT OPEN ERROR
25
Air pressure switch doesn’t open within 30 seconds
A35
AIR PRESS SW NOT CLOSED ER-
ROR
26
Air pressure switch doesn’t close within 30 seconds
A37
UV SENSOR BROKEN
11
UV scanner not functioning
A38
MOD BACK DIFF ERROR
4
Large difference between return and flow temperatures
A39
RAPID RISE ERROR LOCK RET
15
Return temperature rise too rapidly
A40
RAPID RISE ERROR LOCK FLOW
7
Flow temperature rise to rapidly
A41
RAPID RISE ERROR LOCK HX
17
Heat exchanger rise to rapidly
A43
LOW WATER CUTOFF ERROR
30
Water pressure is to low
A44
FLAME CKT ERROR
34
Ionization (flame rod)wire lost for more than 15 se-
conds
Summary of Contents for 1004905923
Page 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Page 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Page 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Page 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Page 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...