MODU-FIRE
®
Forced Draft Gas-Fired Boiler 2500-3000
7
2.5.2
Burn, Fire, and Explosion Hazards
NOTE
Make sure this union is
tight before closing cabinet
cover after servicing boiler.
Reorder No. 8032-02NHAK
c
1998 HCS, Inc. 800-748-0241
NOTE
Reorder No. 8032-01NHPK
c
When opening leak test valves,
always follow instructions in
operation and safety manual.
1998 HCS, Inc. 800-748-0241
Burn, fire, and explosion hazards! Installation must be in strict conformance to all applicable codes and
standards including NFPA 54/ANSI Z223.1 and/or CAN/CSA- B149.1.
Hazard from incorrect fuels! Possible fire, explosion, overheating, and damage. Do not use any fuels except
the design fuel for the unit.
Overfire hazards! High pressure in gas or propane supply could result in overfiring of other devices supplied
from the same source.
Fire and explosion hazards! Close the main gas shutoff before servicing boiler.
Fire and explosion hazards! Do not store or use gasoline or other flammable vapors or liquids in the vicinity
of this or any other gas fired appliance.
Burn hazard! Possible hot surfaces. Do not touch the stack during firing operations. Use only factory
recommended vent components.
Burn hazard! Hot fluids. Use caution. Allow boiler to cool before servicing or draining boiler.
Fire and explosion hazards! Use caution when servicing burner or heat exchanger. Unburned fuel may linger
in the combustion chamber, vent lines, or elsewhere.
Gas leak hazard! Make sure all connections to main burner are tight when reassembling the burner.
Gas leak hazard! All threaded gas connections must be made using a pipe compound that is resistant to
liquefied petroleum.
Do not
use Teflon tape on threaded gas piping.
Gas leak hazard! Check entire gas train for leaks after installation. If there is a smell of gas, shut down the
boiler, close all gas valves and obtain immediate assistance from factory-trained personnel and/or your local
fire department.
Overfire hazard! Possible fire and explosion from excess gas pressure. Make sure that gas inlet pressure
does not exceed 14 inches W.C. to the boiler main gas valve.
Overfire hazard! Possible fire and explosion. Possible malfunction of regulators and/or gas valves.
Maintain all gas train components in good condition. Do not alter wiring connections. Annual inspection by
factory-trained personnel for proper set-up and operation is recommended.
Overfire and underfire hazards! Possible fire, explosion, overheating, and component failure. Do not attempt
to adjust firing rate of the boiler. The firing rate must be adjusted
only
by factory-trained personnel.
Reorder No. 6020-V2WHPK
Improper use may
result in fire or injury.
Read instructions/safety
manual before installing,
operating or servicing boiler.
c
!
WARNING
1998 HCS, Inc. 800-748-0241
Summary of Contents for 1004905923
Page 2: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 2 ...
Page 45: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 45 6 1 3 Wiring Schematic ...
Page 48: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 48 6 1 6 Rear Junction Box ...
Page 49: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 49 6 1 7 Customer Connections ...
Page 56: ...MODU FIRE Forced Draft Gas Fired Boiler 2500 3000 56 ...