CAUTION:
When withdrawing
gas from the cylinder,
the capacity of the
internal vaporizer can
be exceeded. If gas is
withdrawn at rates
greater than the
vaporizer capacity,
liquid or very cold gas
will be discharged.
Severe damage to
external equipment
could result from the
extreme cold.
RELIEF VALVES AND RECOMMENDED REGULATOR SETTINGS
Relief
Pressure
Normal
Valve
Building
Economizer
Operating
Setting
Setting
Setting
Range
22 psig
N/A
N/A
0-22 psig
1.5 bar
N/A
N/A
0-1.5 bar
152 kPa
N/A
N/A
0-152 kPa
230 psig
125 psig
145 psig
125-230 psig
16 bar
8.6 bar
10 bar
8.6-16 bar
1586 kPa
862 kPa
1000 kPa
862-1586 kPa
350 psig
300 psig
320 psig
300-350 psig
24 bar
20.7 bar
22 bar
20.7-24 kPa
2413 kPa
2069 kPa
2206 kPa
2069-2413 kPa
Part numbers for alternate valves and regulators are shown in the Spare Parts section of
this manual.
Pressure
Building Rates
Graph